catalogue search
|
You may also be interested in
Redundancy module, Voltage rectifier, Rectifier module, Controller, Relay
Text version of the page
SNT4612 SNT4624
583814 583815
12 VDC 24 VDC
10,0 - 15,5 VDC 22,5 - 30,0 VDC
3,0 A 1,5 A
36 Watt 36 Watt
86% 88%
76x90x78 76x90x78
approx.
0,75 kg
approx.
0,75 kg
P.O. Box 1521
D - 22905 Ahrensburg
Phone:
+49
+49 4102 42082
Fax: 4102 40930
E-mail : info@feas.com
Internet: www.feas.com
as at 20 December 2007
Switch mode DC power supply SNT46
Output data
Control data
Operating data
Safety devices
Safety data
Applied design specifications
Input data
Mechanical data
Technical data
Input voltage AC 85 - 270 V 400 AC (0- Hz)
Input voltage DC 120 - 400 VDC
Input current at nominal load at 115 V max. 0,55 A / at 230 V max. 0,25 A AC AC
Input current peak
Protective circuit
Hold-up time
380.000 h
Test voltage transformer
High voltage resistance
5 kV according to VDE 0551 AC
primary- / secondary circuit 3,75 kV acc. to VDE AC
Degree of EMI suppression
Protection class
according to VDE 0871B, EN 55022/B
class 1, with PE connection (EN 60950)
Extra low safety potential
Ambient humidity
PELV (EN60204), SELV (EN 60950)
95% relative humidity, yearly average dewing
allowed for use in tropical atmosphere
IP 65
IP 20 (BGV A3)
>30g at 33Hz in X,Y and Z, acc. to IEC 60068-2-27
Protection class enclosure
Protection class terminals
Vibration proof
according to VDE VDE 0100, 0110, 0113, 0551, 0160/W2, 0806
IEC IEC 60950,IEC61000-6-1-2-3-4,IEC60068-2-3
IEC 60068-2-11-52,IEC 60529,IEC 380
EN EN60950,EN61000-6-1,EN61000-6-2,
EN61000-6-3,EN61000-6-4,EN50178,EN55022
EN55011,EN61000-3-3,EN50204,EN61558-2-17
EN60204,EN60529,EN61000-4-2-3-4-5-6-8-11
EN60068-1,EN60068-2-1-2-3-6-27-30
EN45501,EN50021
CSA / UL CSA-C 22.2 / UL60950, UL508, UL1950
Mounting
Nominal output voltage
Range of adjustment
Type
Nominal output current
Power
Efficiency
Dimensions (W x H x D)
Weight
Order number
- compliant
Output separeted according to VDE0551
Extra low safety potential
PELV (EN 60204), SELV (EN 60950)
Overload- and open-circuit protected,
short circuit proof
Parallel connection possible
Protected against reverse voltage at the output
Suitable for the tropics - Epoxy resin casted
Operating status shown by LED
Safety acc. to VDE, EN, UL, CSA
on rails according to DIN 46277 or wall mounting
with screws
|