Solid-state contactor
Type HR3.2.230.20-400
Technical data
Date of issue: 01 October 2009
Protective devices
Varistor, integrated
Varistor, integrated
Integrated into device
Max. 450A˛ x 10ms (superfast for semiconductors)
PUR-resin, non-halogen and self-extinguishing
Protective devices control circuit
Protective devices load circuit
Thermal overload protection
Fuse assignments load circuit
Insulating-grouting
Control circuit
75VAC ..... 270VAC (44 - 66Hz)
60VDC ..... 300VDC
max. 5mA
50g with 33Hz in x, y and z, acc. to IEC 60068-2-27
Degree of protection housing
Degree of protection terminals
Resistance against shock
Applied design specifications
Pollution degree 2 - IEC 60 664-1
IEC/EN 60 529
IEC/EN 60 068
IEC 60068-2-27
Degree of protection terminals
Resistance to climatic conditions
Resistance against shock
EMC
Electrostatic Discharge (ESD)
HF - Irradiation
Surge transients
IEC/EN 61 000-6-4, IEC/EN 61000-6-1
8kV - air / 6kV terminal IEC/EN 61000-4-2
20V/ m IEC/EN 61000-3-4
4kV IEC/EN 61 000-4-5
CSA / UL CSA-C 22.2 / UL60950, UL508, UL1950
Mechanical data
Dimensions (W x H x D) 73.5mm x 107mm x 118mm
Weight 1.28kg
On 35mm DIN-rail acc. to IEC/EN 60 715
Terminal cross-section (control-circuit)
Terminal cross-section (load-circuit)
Tightening torque
Mounting
0.2mm˛ ..... 2.5mm˛ / AWG 24-12 (unfiliar + flexible)
0.2mm˛ ..... 4.0mm˛ / AWG 24-12 (unfiliar + flexible)
0.5Nm ..... 0.6Nm
Postfach 1521
D - 22905 Ahrensburg
Phone: +49 4102 42082
Fax: +49 4102 40930
E-mail: contact@feas.com
Internet: www.feas.com
Main current circuit
48VAC ..... 660VAC
3x 20A at T = 25°C eff U
Voltage-range of load circuit
Max. steady load current
100mA
44Hz ..... 66Hz
380.000h
Selfcooling (natural convection),
Duty cycle
MTBF at 25°C
Cooling
15mm clearance recommended
Load current in A
0 2
0
10
20
30
40
50
4 6 8 10 12 14 16 18 20
Power loss in W
Power dissipation in dependence of load current
Ambient temperature in °C
-10 0
0
5
10
15
20
25
10 20 30 40 50 60 70 80 90
Load current in A
Allowable load current
in dependence of the ambient temperature
Schematic diagram
T
13 14
ZC
IO
current control
T1
L1
mains,
load
A1
control
input
A2
(+)(~)
(-)(~)
ZC
IO
ZC
IO
T2
L2
mains,
load
T3
L3
mains,
load
compliant
107.0
73.5
118.0
|
|