Product specification
DC-UPS: LDR8024
P.O. Box 1521
D - 22905 Ahrensburg
Phone: +49 4102 42082
Fax: + 49 4102 40930
e-mail : info@feas.com
Internet: www.feas.com
as at 17. January 2008
- compliant
Extra low safety voltage
PELV (EN 50178) SELV (EN 60950)
Input 85 - 270 V or 120 - 400 V AC DC
Safety acc. to VDE, EN, UL, CSA
High storage capacity, safeguard against total discharge
PFC acc. to IEC/EN 61000-3-2
Vibration proof, suitable for the tropics
epoxy resin casted
Buffering of 24V-systems
Conforms to VDE0551
No charger necessary
Manual shutdown possible when running in buffer mode
Short circuit proof, overload- and open circuit protected
Operating status shown by LED
Application
Functional principle
Design
first operation
mulator light
After a power failure and the return of the line voltage afterwards the
maximal output current is available immediately. Simultaneously the
accumulator is charging. mulator
The internal power supply is completly casted, if necessary the
accumulators can be replaced easily. The LDR is delivered in an
aluminium housing forwall mounting with screws.
The DC-USV with electronic charging controller LDR8024 is used
for buffering 24V-systems.
The LDR is connected between the line voltage and the system, to
power it with DC voltage. If the line power fails, the system is supplied
from the lead-acid-accumulators, which are integrated in the LDR.
The duration of the supply depends on the quantity of the load current
of the system.
During mains operation the internal switch mode power supply
supplies the DC-consumer and simultaneously charges the
accumulators with optimal loading techniques.
Thereby the output voltage follows the accumulator voltage.
During mains operation and emergency operation an output current
of 10.0 Amp. at 24 V can be obtained permanently. Temporary the
output current can exceed the nominal current up to 25%. The output
is short circuit proof and protected against polarity reversal. To avoid
an unallowable heating of the accu, the LDR is equipped with a
temperature-depending power reduction control.
At the of the LDR, the accumulator is charged. When
the accu is charged, the LED “Akku voll” will green.
When fully charged, the accu is
switched to trickle charging to compensate the loss of selfdischarging.
DC
Please read the data sheets and the operating
instructions for further information.
Automatic accumulator test
imple accumulator exchange
,
s
Remote
monitoring
Relay 1
Relay 2
Input
+-
1
3
2
4
withdrawable capacity in % of the nominal
capacity at different temperatures
100
0°C
20°C
-10°C
-20°C
80
60
40
20
0
0 3 6 9 12 15 18 21 24 27 30 33 36 39 42
capacity (% C)
discharge current x 0,1 CA
|
|