No overcharging
Safeguard against total discharge
Safety acc. to VDE, EN, UL, CSA
Messages with remote monitoring
Operating status shown by LED
High storage capacity NiMH-accumulators
No charger necessary
Vibration proof, suitable for the tropics
Buffering of 12V-systems
product specification
DC - UPS: LDR2012
Postfach 1521
D - 22905 AHRENSBURG
phone: +49 4102 42082
telefax: +49 4102 40930
e-mail: info@feas.com
internet: www.feas.com
The accupac with electronic charging controller LDR2012
is used for buffering 12V-systems.
The accupac LDR is connected between the unregulated DC power supply
and the powered system. If the line power fails, the system is supplied from
the NiMH-accumulator, which is integrated in the LDR. The duration of the
supply depends on the quantity of the load current of the system.
During mains operation the internal DC-DC converter supplies the
DC-consumer system and simultaneously charges the accumulator with an
optimal loading technique.
Thereby the output voltage follows the accu voltage. During mains
operation and emergency operation an output current of 1.8 Amp. at 12 V
can be obtained permanently. Preferably, the LDR is powered with the FEAS
power supply PSLC283.
When supplied from a FEAS power supply, the LDR can be operated
directly at the power source.
DC
At the of the LDR, the accumulator is charged. This is
shown by the LED “charging”. will green
ill red, when the batteries
are nearly discharged and before the LDR’s protection against low discharge
will switch off the system. The system is then unsupplied.
When fully charged, the accu is switched to trickle charging to
compensate the loss of self-discharging. is now ready for operation.
first operation
yellow The LED “Line” light , when
a line voltage is detected. The lower LED w light
DC-consumer
To enable remote monitoring of the accupac, it has 2 build-in relays.
After a power failure and the return of the line voltage afterwards the
maximal output current is available immediately. Simultaneously the accu is
charging.
The LDR
The LDR is delivered in a flame resistant plastics housing for mounting
on a rail according to DIN 46277 or for wall mounting with screws.
Application
Functional principle
Design
Please read the data sheets
and the operating instructions
for further information.
withdrawable capacity in % of the nominal
capacity at different temperatures
100
0°C
20°C
-10°C
-20°C
80
60
40
20
0
0 3 6 9 12 15 18 21 24 27 30 33 36 39 42
capacity (% C)
discharge current x 0,1 CA
max. current drain LDR2012: 1.8 Amp.
consumer
DC-input
18.0V - 50.0V DC DC
+ -
relay contacts for
remote monitoring
relay contacts for
remote monitoring
Wide range input voltage
Relais 1
Relais 2
+
NO
NC
COM
- - - + +
NO
NC
COM
- - + +
Kurzschlussfest !
Short-circuit proof!
Netz
Line
charging
Green - DC OK
Red - Accu protection
|
|