Best Practices Engineering Guide: Installation Recommendations for FCI Single-Point, Thermal Dispersion Flow Meters |
![]() |
Best Practices Engineering Guide: Installation Recommendations for FCI Single-Point, Thermal Dispersion Flow Meters p 1 Best Practices Engineering Guide Installation Recommendations for FCI Single-Point, Thermal Dispersion Flow Meters N Straight-Run Situations and Recommendations N Installation Orientation Options f... |
![]() |
Best Practices Engineering Guide: Installation Recommendations for FCI Single-Point, Thermal Dispersion Flow Meters p 2 FCI Offers Multiple Solutions to Limited Straight-Run Conditions Straight-run is one of the most significant variables to consider in your flow meter installation to ensure accurate and repeatable f... |
![]() |
Best Practices Engineering Guide: Installation Recommendations for FCI Single-Point, Thermal Dispersion Flow Meters p 3 Swirl Reduction Tabs – The swirl reduction tabs remove swirl by generating small vortices (swirls) opposite to the main swirl. These cumulatively cancel the larger main swirl. Profile Condition Tabs ... |
![]() |
Best Practices Engineering Guide: Installation Recommendations for FCI Single-Point, Thermal Dispersion Flow Meters p 4 Figure 4: Pipe Installation Orientation Options for Insertion Style Flow Meters Installation in Horizontal Pipe: For General Air/Gas Applications Top MountedBottom MountedSide Mounted Angled at 45°... |