Pulse™ Series Control Instruction Manual
Range for % power setpoint: 0 to 100%
Description: When a zone is in Manual Mode and a zone's setpoint is set lower than the setpoint setup in the LO-MN column, the setpoint is prevented from being lowered below the setpoint limit in LO-MN. As a warning, a small pop-up appears just above the function keys at the bottom of the screen (reference diagram below). The warning shows an "Under Power Limit of X"; to the right of this message is a tag for function button F4 reading "BACK". Pressing the BACK button will clear the warning.
For example: If a LO-MN limit of 5% is set and an attempt is made to lower the zone's % power setpoint (SET) below this, the limit warning will pop up above function keys F1 to F3 and indicate "Under Power Limit of 5.
Note: LO-MN must always be set lower than HI-MN or setpoint will be completely prevented from changes.
QUICK REFERENCE
GETTING STARTED ................4
Unpacking Your Pulse ................4
What's Included..........................4
Pulse Cabinets............................5
Pulse Modules............................6
Heater & T/C Mold Cables..........8
Connecting AC Power................9
ABOUT..................................10
System Operation....................10
22 CAV22 300F 300F 010% 02.0A MANUAL
23 CAV23 300F 300F 010% 02.0A MANUAL
24 CAV24 300F 300F fiTTitfl 02.0A MANUAL
Pulse Screens............................12
Help ........................................14
Main Screen ............................15
Zone Setup Parameters............18
System Setup Screen................31
File System ..............................34
Security....................................35
Alarm......................................38
Printing....................................40
HOW TO................................41
Shutting OFF the Alarm............41
Setting Up Multiple Zones........41
Troubleshooting........................42
SPECIFICATIONS ..................43
General....................................43
System ....................................43
WARRANTY ..........................44
Under Power Limit of 10 BACK
Column 7: HI-MN "Setpoint Manual Mode (% Power Control) HIGH End Setpoint"
Range for % power setpoint: 0 to 100%
Description: When a zone is in Manual Mode and a zone's setpoint is set higher than the setpoint setup in the HI-MN column, the setpoint is prevented from being raised above the setpoint limit in HI-MN. As a warning, a small pop-up appears just above the function keys at the bottom of the screen (reference diagram below). The warning shows an "Over Power Limit of X"; to the right of this message is a tag for function button F4 reading "BACK". Pressing the BACK button will clear the warning.
For example: If a HI-MN limit of 60% is set and an attempt is made to raise the zone's % power setpoint (SET) above this, the limit warning will pop up above function keys F1 to F3 and indicate "Over Power Limit of 60).
Note: LO-MN must always be set lower than HI-MN or setpoint will be completely prevented from changes.