Pulse™ Series Control Instruction Manual
Range for temperature setpoints: 0 to 999 deg F or 0 to 999 deg C. Description: When a zone is in Auto Mode and a zone's setpoint is set lower than the setpoint setup in the LO-AT column, the setpoint is prevented from being lowered below the setpoint limit in LO-AT. As a warning, a small pop-up appears just above the function keys at the bottom of the screen (reference diagram below). The warning shows an "Under Temp Limit of X"; to the right of this message is a tag for function button F4 reading "BACK". Pressing the BACK button will clear the warning.
For example: If a LO-AT limit of 50F is set and an attempt is made to lower the zone's temperature setpoint (SET) below this, the limit warning will pop up above function keys F1 to F3 and indicate "Under Temp Limit of 50.
Note: LO-AT must always be set lower than HI-AT or setpoint will be completely prevented from changes.
SECTION REFERENCE
ABOUT..................................10
System Operation....................10
RUN........................................10
STOP........................................10
BOOST....................................10
IDLE ........................................11
Navigate/Change Values..........11
Pulse Screens............................12
Help ........................................14
Main Screen ............................15
Zone Main Setup......................18
Zone Limits Setup....................21
Zone Boost/Idle Setup..............25
Zone PID Setup........................28
System Setup Screen................31
File System ..............................34
Security....................................35
Security Setup..........................36
Alarm......................................38
Printing....................................40
CAV22 CAV23 CAV24
300F 300F
010% 010% 010%
02.0A AUTO 02.0A AUTO 02.0A AUTO
Under Temp Limit
Column 5: HI-AT "Setpoint Auto Mode (Temperature) HIGH End Setpoint"
Range for temperature setpoints: 0 to 999 deg F or 0 to 999 deg C. Description: When a zone is in Auto Mode and a zone's setpoint is set higher than the setpoint setup in the HI-AT column, the setpoint is prevented from being raised above the setpoint limit in HI-AT. As a warning, a small pop-up appears just above the function keys at the bottom of the screen (reference diagram below). The warning shows an "Over Temp Limit of X"; to the right of this message is a tag for function button F4 reading "BACK". Pressing the BACK button will clear the warning.
For example: If a HI-AT limit of 700F is set and an attempt is made to raise the zone's temperature setpoint (SET) above this, the limit warning will pop up above function keys F1 to F3 and indicate "Over Temp Limit of 700. Note: LO-AT must always be set lower than HI-AT or setpoint will be completely prevented from changes.
Column 6: LO-MN "Setpoint Manual Mode (% Power Control) LOW End Setpoint"
22 CAV22
23 CAV23
24 CAV24
010% 010% 010%
02.0A AUTO 02.0A AUTO 02.0A AUTO
300F 300F
Over Temp Limit