Primary Airfield Lighting Cables Screened

versus

Non-Screened

Two different types of cables are used in primary airfieldlighting circuits:- non-screened cables and - screened cables.Classically both cables have a single AWG 8 copper conductor or a cross section of 6.0 mm 1. CCR, transformer, lights and cable The fig. 1 shows a typical primary airfield lighting circuit,where a constant current regulator (CCR) feeds the primaryairfield cable, the transformers and the lights.
2 . In most cases, theconductor is equipped with a conductor shield formed by a semi-conductive layer, covered by an XLPE insulation.Typically the non screened cable has no outer sheath. The screened version has another semi-conductive layerabove the XLPE insulation covered by a metallic screen (braid or metallic foil) and an outer sheath.Both cables perform well in primary airfield lighting circuits.Nevertheless, the non-screened cable shows a rather high sensitivity to the tracking phenomenon under specific circumstances, leading to service interruption of the lighting circuit. Fig. 1