29
Safety System MGB-...-AR...
Subject to technical modifications; no responsibility is accepted for the accuracy of this information.
MGB-AR
MGB-L0...
1 2
3
Terminal assignment cable entry Terminal assignment plug connector RC18
Pin Designation Description
1 - Not used
2 IA
Enable input for channel A, connect to DC 24 V
in separate operation. In case of switch chains,
connect output signal OA from previous device.
3 IB
Enable input for channel B, connect to DC 24 V
in separate operation. In case of switch chains,
connect output signal OB from previous device.
4 OA
Safety output channel A,
ON when the door is closed and the bolt tongue
is inserted in the interlocking module.
5 OB
Safety output channel B,
ON when the door is closed and the bolt tongue
is inserted in the interlocking module.
6 UA
UB
Power supply, DC 24 V
7 RST Reset input, device is reset if DC 24 V are applied
to RST for at least 3 s.
8 O2
Bolt tongue monitoring output,
ON when the door is closed and the bolt tongue
is inserted in the interlocking module.
9 O4 Monitoring output DIA2,
ON when the device is in the fault state.
10
- See wiring diagram B
11
12 - Not used
13
See wiring diagram B for controls and indicators.
14
15
16
17
18
19 0 V Ground
Terminal Designation Description
X2.1 to X2.7 - See wiring diagram A for controls and indica-
X3.1 to X3.3 - tors.
X3.4 UA
Power supply for the monitoring outputs, DC
24 V
X3.5 0 V Ground (connected internally to X5.5).
X3.6 - Not used
X3.7 - Not used
X4.1 IA
Enable input for channel A, connect to DC 24 V
in separate operation. In case of switch chains,
connect output signal OA from previous device.
X4.2 IB
Enable input for channel B, connect to DC 24 V
in separate operation. In case of switch chains,
connect output signal OB from previous device.
X4.3 - Not used
X4.4 OA
Safety output channel A,
ON when the door is closed and the bolt tongue
is inserted in the interlocking module.
X4.5 OB
Safety output channel B,
ON when the door is closed and the bolt tongue
is inserted in the interlocking module.
X4.6 RST Reset input, device is reset if DC 24 V are applied
to RST for at least 3 s.
X5.1 O1 Door monitoring output,
ON when the door is closed.
X5.2 O2
Bolt tongue monitoring output,
ON when the door is closed and the bolt tongue
is inserted in the interlocking module.
X5.3 - Not used
X5.4 O4 Monitoring output DIA2,
ON when the device is in the fault state.
X5.5 0 V Ground (connected internally to X3.5)
X5.6 UB Power supply, DC 24 V
|