Solid State Remote Power Controller E-1048-S6xx - 1

www.e-t-a.com Solid State Remote Power Controller E-1048-S6xx Issue C 5 - 7 6 Description Features Technical data (Tambient = 25 °C; at UN) Ordering information E-1048-S602 Load circuit Voltage rating US DC 24 V (18...36 V) Current rating IN 0.5 A; 1 A; 2 A; 4 A (other ratings to special order) Closed-circuit current IContr typically 0.3 mA Min. load current Standard version: Iload > 1 mA wire break indication in OFF condition Option: wire break indication in OFF and ON condition wire break ind. in OFF cond. Rload > typ. 500 kÙ wire break ind. in ON cond. Iload < typ. 130 mA (0.5/1 A unit) Iload < typ. 500 mA (2/4 A unit) Voltage drop UDSmax 0.15 V; 0.3 V; 0.1 V; 0.2 V Switch-on/switch-off time ton/toff typ. 300 ìs/700 ìs with resistive load Overload disconnection approx. 1.5 (±0.3) x IN after approx. 100 ms Short-circuit current max. 25 A (with 0.5 A and 1 A (self-limiting) current ratings) max. 75 A (with 2 A and 4 A current ratings) Short-circuit disconnection < 250 ìs Control circuit Voltage rating DC 24 V Voltage controlled input UE DC 0 V < low level < 5 V DC 8.5 V < high level < 36 V Input current IE 1...10 mA (8.5...36 V) Max. switching frequency fmax 500 Hz Reset time after shortcircuit/ overload disconnection 1 ms Fault indication output F (opto coupler) Voltage rating range DC 5...36 V Voltage rating range DC 5...36 V Max. load current 100 mA (ÄU < 2 V), with reverse polarity protection Error indication output F+ / F- conductive - wire break in load circuit - after short-circuit/overload disconnection Parallel connection possible, as leakage current < 10 ìA General data Temperature range 0 °C...+60 °C Insulation voltage 2.5 kVrms (IEC 60664/VDE 0110) Vibration 3 g, test to EN 60068-2-6 test Fc Mass 34 g Type No. E-1048 Solid State Remote Power Controller Version S600 wire break indication in OFF condition (standard) S602 with permanent wire break monitoring Voltage rating DC 24 V DC 24 V (standard) Current ratings 0.5 A 1.0 A 2.0 A 4.0 A E-1048 - S600 DC24 V 1.0 A ordering example Where remote control, wire break and LED indication is not required, please contact us for a thermal-magnetic circuit breaker (e.g. types 2210, 3600, 3900). The E-T-A Solid State Remote Power Controller (SSRPC) E-1048-S6xx is an opto decoupled transistorised switching device providing both protection and signalisation. It may be used wherever safe switching and protection of resistive, inductive or lamp loads in DC voltage systems is required. Typical applications Automation - interface module providing inexpensive power amplification at PLC outputs - optimum protection of individual loads by monitoring the load circuit Protection and control of - motors - solenoids - lamps œ Optimum load protection. Available in current ratings of 0.5 A; 1 A; 2 A; 4 A. No derating required over entire temperature range! œ Fast short-circuit limitation and disconnection œ Time/current dependent overload disconnection (simulating thermal-magnetic CBE trip curve) œ Remote control œ Fault indication: LED and signal output for overload/short-circuit signalisation, and wire break indication in the OFF condition (version -600) and in the OFF and ON condition (version -602) œ Physically isolated fault indication. œ Compact plug-in type WEN

Open the catalog to page 1
Solid State Remote Power Controller E-1048-S6xx - 2

www.e-t-a.com Solid State Remote Power Controller E-1048-S6xx 5 - 8 Issue C 6 10 20 1000 100 10 1 0.1 30 Trip time in ms I (A) current limitation IN 20 40 1000 100 10 1 0.1 60 Trip time in ms I 80 I (A) N current limitation 0.5 A and 1 A 2 A and 4 A Technical description Status indication Dimensions Connection diagram Typical time/current characteristics (TA = 25 °C) 7 3 2 5 control and monitoring electronics F + F - control circuit red green load Q -US 4 6 1 +US E-1048-S600 IN+ INfault output Fault indication output (opto coupler) LED green r ed non-conductive, no duty conductive, normal...

Open the catalog to page 2
Solid State Remote Power Controller E-1048-S6xx - 3

www.e-t-a.com Solid State Remote Power Controller E-1048-S6xx Issue C 5 - 9 6 Functional diagrams E-1048-S6xx wire break Error indication opto coupler LED red LED green IN US Version output Error 0 1 0 1 Operating voltage is applied E-1048-S600 wire breakage monitoring only in OFF condition Functional diagram E-1048-S6xx wire break indication wire break Error indication opto coupler LED red LED green IN US Version output Error 0 1 0 1 Operating voltage is applied E-1048-S602 wire breakage monitoring in ON and OFF condition 0 1 * Fault indication is reset when control coltage is switched...

Open the catalog to page 3
Solid State Remote Power Controller E-1048-S6xx - 4

www.e-t-a.com Solid State Remote Power Controller E-1048-S6xx 5 - 10 Issue C 6 Accessories for E 1048-S6xx 9 5.4 125 17 .669 .213 .354 4.92 2 cylinder head screw M4x4 ISO1207 nickel plated washer A 4.3 DIN 125 nickel plated female connector Phoenix terminal AKG 35 max.cross section 35 mm2 (AWG 2) M4 10 7 12.8 154.8 pressure-relief joint (1.1 mm (.043 in.) thick constriction) Cu rail, tin-plated .394 .079 .276 .504 6.09 blade terminal DIN 46244 part 2 C profile (2xA2.8-0.8) (QC 2x.110) depth 10 mm (.394 in.) adapter X20040901 symmetrical rail EN 50022-35x7.5 polarization recess G-profile EN...

Open the catalog to page 4

All E-T-A catalogs and technical brochures

  1. MPR10, MPR20

    5 Pages

  2. CATALOGUE

    108 Pages

  3. CPC20

    12 Pages

  4. CPC12

    8 Pages

  5. REX12

    16 Pages

  6. PC10IO

    2 Pages

  7. PC10PN

    4 Pages

  8. PC10PB

    4 Pages

  9. SVS18

    6 Pages

  10. 1140-E

    4 Pages

  11. 1110

    2 Pages

  12. 129-L11-H-KF

    2 Pages

  13. 127

    4 Pages

  14. 104

    4 Pages