ERL Input/Output Expansion Module
5Pages

{{requestButtons}}

Catalog excerpts

ERL Input/Output Expansion Module - 1

ERL Input/Output Expansion Module ERL I/O Product Overview The ERL I/O expansion module is a digital input / output extension box which supports 128 physical digital inputs (DIs) and 15 output contacts. The I/O module uses IEC 61850-8-1 station bus protocol GOOSE messages to publish the state of the binary inputs to other ERL Devices and any other IEDs supporting IEC 61850 GOOSE subscriptions. The I/O module can also trigger on the state of digital inputs in GOOSE messages published by ERL devices and other IED’s to activate its 15 user configurable output contacts or create records on any of its 128 virtual input channels. The ERL I/O Expansion system consists primarily of the unit hardware and the TESLA Control Panel user interface software. TESLA Control Panel user interface software provides tools to configure the unit, retrieve and manage records and display real time digital status values. Control Panel also includes RecordGraph, a graphical record display and analysis software tool. ERL 61850 IED Configurator software provides tools to manage unit’s station bus configuration. Application: The ERL I/O module is to be used in any application where there is need for many status (DI) inputs – such as large substations and generating stations. By communicating these digital input statuses to multiple IED’s in the network it expands their access to such information and is a cheaper alternative to adding additional IED’s. It reduces the problems associated with having these multiple IED’s communicate with each other and also reduces the cost. The ERL I/O IED also provides alarm and control through its 15 output contacts and 15 subscription virtual channels for output contact control. ERL I/O Expansion Module 10 Year WARRANTY

Open the catalog to page 1
ERL Input/Output Expansion Module - 2

Application with TESLA 4000 TESLA 4000 power system recorder has provision for up to 256 virtual inputs which can be mapped to receive and record the time and status of events contained in the IEC 61850 GOOSE messages published by the ERL I/O module. These messages are available for records and oscillography in the same way as the 64 physical status (digital) inputs of the TESLA. Connect two ERL I/O modules with each TESLA 4000 to monitor and record 256 additional digital inputs. Use the Windows based ERL 61850 IED Configurator to configure and map data between the ERL I/O IED and TESLA 4000....

Open the catalog to page 2
ERL Input/Output Expansion Module - 3

Features • 128 external (digital) input channels with event tracking which can be published as an IEC 61850 GOOSE status message • 15 user-configurable output contacts which can be activated by GOOSE or DNP3 Binary Output triggers • 128 Virtual inputs to trigger and record on subscribed GOOSE messages • Real-time metering display shows all input statuses • 500 entry event log (circular) • 19” rack-mount format, 4U footprint Communication Protocols • Standard TCP/IP communication protocol to communicate with TESLA Control Panel • SCADA protocol DNP3 over Ethernet or Modbus over serial • IEC...

Open the catalog to page 3
ERL Input/Output Expansion Module - 4

Detailed SpecificationsERL Digital I/O Expansion Module Item General Weight Dimensions Nominal Frequency Power Supply Rack mount Maximum current: 0.7 A Maximum burden: 35 W Sample Rate A/D Resolution Recording and Logging: Transient Fault Record Storage Event Logging Channels and Triggers GOOSE Virtual Inputs (digital) Interface & Communication Front Panel Indicators 96 samples/cycle (s/c) 16 bits, 65536 counts full scale Record Length 0.2 to 15 seconds, 30 second extended Up to 150 records 500 events in the regular log Active, Inactive or both 6 LEDs Unit Functional, IRIG-B Functional,...

Open the catalog to page 4
ERL Input/Output Expansion Module - 5

ERL Digital I/O Expansion Module Item Environmental Ambient Temperature Range Humidity Insulation Test (Hi-Pot) -40°C to 85 °C Up to 95% without condensation Power supply, external inputs, output contacts -2 kV, 50/60 Hz, 1 minute Electrostatic Discharge Voltage Dips, Interruptions, Variations Conducted RF Immunity Radiated RF Susceptibility Electrical Fast Track/Burst Oscillatory Transient Oscillatory Vibration Seismic Shock and Bump RF Emissions Conducted Emissions ERLPhase Power Technologies Tel: 204-477-0591 Email: info@erlphase.com The specifications and product information contained...

Open the catalog to page 5

All ERLPhase catalogs and technical brochures

  1. T-PRO 4000

    8 Pages

  2. L-PRO

    8 Pages

  3. S-PRO 4000

    9 Pages

  4. L-PRO 4000

    9 Pages

  5. F-PRO

    8 Pages

  6. B-PRO 4000

    8 Pages

  7. TESLA LITE

    5 Pages

  8. TESLA 4000

    8 Pages