Text version of the page
Text version of the page
BASIC ELECTRIC PANELMODELLB 180 SERIES MODELNUMBER > LB-100-2 LB-120-2 LB-150-2 LB-180-2 LB-240-2 LB-150-3 LB-180-3 LB-240-3 Electric Rating KW 200 240 300 360 480 450 540 720 Start up Amperage (220 3ø) 556 668 834 950 1336 1251 1500 2004 Start up Amperage (440 3ø) 264 318 394 474 636 591 711 948 Developed Boiler Horsepower 20 24 30 36 48 45 54 72 *Steam Capacity (from & at 212°F) 690 824 1034 1242 1648 1551 1863 2484 Gross BTU Output (100% Rating) > 670,000 804,00 1,400,600 1,205,200 1,608,000 1,506,800 1,807,800 2,412,000 Number of Sections 2 2 2 2 2 3 3 3 Developed BHPPer Section 10 12 15 18 24 15 18 24 DIMENSIONS Height 76 76 76 76 76 76 76 76 Length 60 60 60 60 60 60 60 60 Width 28 28 28 28 28 28 28 28 Shipping Weight High Pressure Model 1900 1900 1900 1900 1900 2700 2700 2700 Shipping Weight Low Pressure Model 1650 1650 1650 1650 1650 2325 2325 2325 > SUGGESTED SPECIFICATIONS ELECTRICALSPECIFICATIONS - ALLMODELS1. STANDARD UNITS - The Fully Automatic All Electric Steam Professional generator as called for under requirements of this specification shall be as manu-
factured by The Electro-Steam Generator Corporation or equal and shall meet all of the following requirements:1.Generator shall be constructed under the A.S.M.E. Power Code - Section 1 Part PMB (Miniature - 100 lbs. P.S.I. )
2. Each generator shall be shop inspected and stamped by a National Board of Boiler and Pressure Vessels authorized
inspector.
3. ELECTRICHEATERS shall be immersion resistance type - with copper sheathing. Entire element brazed into removable standard 150 lb. test -forged steel flange.
4. U.L. & C.S.A. LISTING - shall cover complete Electric Steam Generator Package with all electric controls mounted on
generator - not acceptable with U.L. & C.S.A. on electric controls only.
5. Standard boiler trim plus combination water and pump regulation- adjustable steam pressure control.
6. All equipment and controls shall be mounted and wired as a complete single package requiring only city water connection, drain line and electric line service at point of installation. AC - 208-240/120 volts, 60 cycle, 3 phase 2. 120/440-480 VOLTS -available in phase 3 - all models. 3. SPECIALELECTRICALREQUIREMENTS - 380,550, 600 volts- 50 cycle - etc. special order upon request. SPECIFYCURRENTCHARACTERISTICS (voltage cycle-phase). **Note No. 1All units require an additional 18" of floor space (length and width) for ideal
plumbing connections and service
**Note No. 2All units require an additional 36” clearance at 5 opening of electric
panel boxes and servicing of electric heaters. ? Explosion Proof? Indirect Steam
? Condensate Return System? 316/316LStainless Steel OPTIONS AVAILABLE ELECTRO-STEAM GENERATOR CORP.1000 BERNARD ST. · ALEXANDRIA, VIRGINIA22314-1299Call Toll Free: 1-800-634-8177Fax Toll Free: 1-888-783-2624PHONE (703) 549-0664 · FAX (703) 836-2581 E-mail: sales@electrosteam.comPHONE (703) 549-0664 · FAX (703) 836-2581E-mail: sales@electrosteam.com
|