video corpo

Surge Protection urge Protection Controlling & Switching Busbar Systems Other Accessories
225Pages

{{requestButtons}}

Catalog excerpts

Surge Protection urge Protection Controlling & Switching Busbar Systems Other Accessories - 1

Eaton www.eaton.eu Surge Protection Controlling & Switching Busbar Systems J Other Accessories' Powering Business Worldwide

Open the catalog to page 1
Surge Protection urge Protection Controlling & Switching Busbar Systems Other Accessories - 2

Surge Protection r ^ EATON CORPORATION xxxxx+xxxx-xxxxEN

Open the catalog to page 2
Surge Protection urge Protection Controlling & Switching Busbar Systems Other Accessories - 3

Surge Protection Surge Protective Class T1+T2+T3,, SPRT12-264 Max. Cont. Operat. Voltage UC Type Designation Combined Surge Protective Device SPRT12-264 incl. FM contact (change-over contact) sg07416 Specifications | Surge Protection Class T1+T2+T3, Description • Ready-to-connect Combined Surge Protection Device Type 1 + Type 2 + Type 3 on the basis of spark gaps • Consisting of the base unit and plug-type modules • Suitable for the protection of end devices EATON CORPORATION xxxxx+

Open the catalog to page 3
Surge Protection urge Protection Controlling & Switching Busbar Systems Other Accessories - 4

xPole Technical Data SPRT12-264/3-AX SPRT12-264/4-AX SPD acc. to EN 61643-11 / ...IEC 61643-11 Type 1 + Type 2 / Class I + II Type 1 + Type 2 / Class I + II Energetically coordinated protection effect to end device (< 5 m) Type 1 + Type 2 + Type 3 Type 1 + Type 2 + Type 3 Rated voltage AC (UN)_230/400 V (50/60 Hz)_230/400 V (50/60 Hz)_ Max. continuous operating voltage AC [L-N] (Uc) 264 V (50/60 Hz) 264 V (50/60 Hz) Max. continuous operating voltage AC [N-PE] (Uc (N-PE)) - - Specific energy [L1+L2+L3+N-PE] (W/R) 1.40 MJ/Ohm 2.50 MJ/Ohm Impulse...

Open the catalog to page 4
Surge Protection urge Protection Controlling & Switching Busbar Systems Other Accessories - 5

ii EATON CORPORATION xxxxx+xxxx-xxxxEN

Open the catalog to page 5
Surge Protection urge Protection Controlling & Switching Busbar Systems Other Accessories - 6

Type Article No. Units per Designation package Lightning current arrester - surge arrester Sets, Lightning protection classes III, IV Without remote indication_ Busbar ZV-KSBI... Impulse current Ijmp (10/350)ps Type Article No. Units per Designation package Lightning current arrester - surge arrester SPBT12 Complete 12,5kA L - (PE) N 50kA N-PE 100kA N-PE Specifications | SPD Class T1&T2 Description • Field of application For the protection of low voltage distribution systems against transient overvoltage caused by direct and indirect lightning stroke and switching...

Open the catalog to page 6
Surge Protection urge Protection Controlling & Switching Busbar Systems Other Accessories - 7

Surge ProtectionTechnical Data Electrical Responding time (rate of voltage rise 5 kV/gs) Voltage protection level Up_ Voltage protection level at 5 kA (8/20) gs Max. continuous operating voltage UC TOV test value UT Rated frequency Open circuit voltage Uoc Nominal discharge current (8/20) gs In Max. Discharge current Imax Impulse current Iimp (10/350) gs Peak current Charge Q Specific energy Follow current interrupt rating Ifi Maximum back-up fuse Maximum short-circuit current Connection diagram Permitted ambient temperature -40°C to +70°C -40°C to +70°C -40°C to +70°C Degree of...

Open the catalog to page 7
Surge Protection urge Protection Controlling & Switching Busbar Systems Other Accessories - 8

xPole Technical Data SPBT12-280-1+NPE50 SPBT12-280-3+NPE50 Electrical Responding time (rate of voltage rise 5 kV/gs) Voltage protection level Up_ Max. continuous operating voltage UC TOV test value UT (5 s) (200 ms)_ Rated frequency Open circuit voltage Uoc Nominal discharge current (8/20) gs In Max. Discharge current Imax Impulse current Iimp (10/350) gs Peak current Charge Q Specific energy Follow current interrupt rating Ifi Maximum back-up fuse Maximum short-circuit current Connection diagram Mechanical Frame size Device height Device width Weight Permitted ambient temperature Degree of...

Open the catalog to page 8
Surge Protection urge Protection Controlling & Switching Busbar Systems Other Accessories - 9

xPole Technical Data SPBT12-280-1+NPE SPBT12-280-3+NPE Electrical Responding time (rate of voltage rise 5 kV/gs) Voltage protection level Up_ Max. continuous operating voltage UC TOV test value UT (5 s) (200 ms)_ Rated frequency Open circuit voltage Uoc Nominal discharge current (8/20) gs In Max. Discharge current Imax Impulse current Iimp (10/350) gs Peak current Charge Q Specific energy Follow current interrupt rating Ifi Maximum back-up fuse Maximum short-circuit current Connection diagram Mechanical Frame size Device height Device width Weight Permitted ambient temperature Degree of...

Open the catalog to page 9
Surge Protection urge Protection Controlling & Switching Busbar Systems Other Accessories - 10

xPole SPD Class T1&T2 (formerly B+C), SPBT12 Max. Cont. Operat. Voltage Uc In (8/20)ps Type Article No. Units per Designation package Plug-in surge arrester SPCT2, 1- to 4-pole Complete (2- and multi-pole surge arresters are supplied with busbar) Plug-in surge arrester SPCT2 EATON CORPORATION xxxxx+xxxx-xxxxEN

Open the catalog to page 10
Surge Protection urge Protection Controlling & Switching Busbar Systems Other Accessories - 11

Surge Protection Description • Field of application: For the protection of low voltage distribution systems against transient overvoltage caused by indirect lightning stroke and switching operations. • Test class [m] according to IEC 61643-1+A1 • SPD-type [T2 according to EN 61643-11 • Auxiliary switch SPC-S-HK for remote message transmission can be mounted onto the device • Suitable for busbar connection to all Xtra Combinations switchgear • Type SPC-S-3+1: consists of 1 base SPC-S-S4-3+1, 1 insert SPC-S-N/PE and 3 inserts SPC-S-20/335 • Type SPC-S-1+1: consists of 1 base SPC-S-S2-1+1, 1...

Open the catalog to page 11
Surge Protection urge Protection Controlling & Switching Busbar Systems Other Accessories - 12

xPole Technical Data Inserts Mechanical coding x Responding time (rate of voltage rise 5 kV/gs) < 25 ns Voltage protection level at nominal discharge current / Uoc < 2.6 kV Voltage protection level at 5 kA (8/20) gs 2000 V Max. continuous operating voltage Uc 580 VAC TOV test value UT = UC (5 s) Nominal discharge current (8/20) gs In 20 kA Max. Discharge current Imax 40 kA Follow current interrupt rating Ifi - Maximum short-circuit current i Connection diagram Mechanical Frame size Device height Device width 1pole 1+1pole 2pole 3pole 3+1pole 4pole Mechanical...

Open the catalog to page 12
Surge Protection urge Protection Controlling & Switching Busbar Systems Other Accessories - 13

xPole Technical Data SPCT2-1+NPE SPCT2-3+NPE Mechanical coding Responding time (rate of voltage rise 5 kV/ps) Max. continuous operating voltage UC TOV test value UT (5 s) (200 ms)_ Rated frequency Nominal discharge current In Voltage protection level Up at In_ Max. Discharge current Imax Follow current interrupt rating Ifi Maximum short-circuit current Connection diagram Mechanical Mechanical coding of base Frame size Device height Device width Weight Upper and lower lift terminal capacity Upper and lower open mouthed terminals for busbar thickness up to Tightening torque of terminal...

Open the catalog to page 13
Surge Protection urge Protection Controlling & Switching Busbar Systems Other Accessories - 14

Surge Arrester Set SPCT2-335-3+NPE/BB • The 3+1 circuit offers a universal solution for surge protection in low voltage distribution systems • Suitable for TT- and TN-S systems according to IEC 60364-5-53 Clause 534 • Remote message transmission is possibly by mounting auxiliary switch ASAUXSC-SPM • Busbar connected, minimum installation work required - 1 unit SPCT2-335-3+NPE surge arrester - 1 unit ASLTT-63 lead-through terminal - busbar included EATON CORPORATION xxxxx+xxxx-xxxxEN