2/16 Contactors for three-phase capacitorsMoeller NK1210+2100+2300-1153GB-INT Three-phase capacitors 50 – 60 HzContact sequence Part no. Price see price listStd. packOpen Article no. 230 V400 V525 V690 V kvarkvarkvarkvar With series resistors without quick-discharge resistor Basic units 7.512.516.720 DILK12-11(230V50HZ) 1 off11202533.3Contactors DILM7 – DILM150 13524613211422A1A2 293988 DILK20-11(230V50HZ) 294010 152533.340 DILK25-11(230V50HZ) 294032 2033.34055 DILK33-10(230V50HZ) 294054 25506585 1352461314A1A2 DILK50-10(230V50HZ) 294076 NotesAvailability on request. Weld-resistant for capacitors with inrush current peaks up to 180 x I N L1L2L3 135642A2A1 R11R11R11C1 Accessories Enclosure Accessories a 2/22 Further actuating voltages a 2/37 In the case of group compensation multi-stage capacitor banks are connected to the mains, as required. In the process, transient currents of up to 180 x I e can flow between the capacitors.The capacitors are pre-charged via the early-make auxiliary contacts and the fitted wire resistors, thereby reducing the inrush current. The main contacts then close after a time lag and carry the uninterrupted current.The contactors for capacitors are weld-resistant with inrush current peaks up to 180 x I e due to their special contacts.For switching reactive-power compensation equipment with chokes, observe design notes.For switching of power factor correction with reactors please observe engeneering notes a 2/17 |