Catalogue BEXA120
www.e2s.com
print switch display
Page / 2
Where to buy
this product ?
Request
a Quote
E2S - 3075
/ 2
See other catalogues for E2S
Text version of the page
t e c h n i c a l s p e c i f i c a t i o n
<5>2S
BExA120 & BExDA120 ATEX EEx Hazardous Area Voice Annunciation unit
warning signals
Nominal output : 113dB(A) @ 1m +/- 3dB - Tone 5.
A120D : EEx d IIC T4 (Tamb. -50 to +55°C)
A120E : EEx de IIC T4 (Tamb. -50 to +55°C)
ATEX / CENELEC / FTZU / GOST R
10 alarm tones (UKOOA / PFEER compliant)
Edits automatically to message length
Easy message creation with built in microphone.
Volume control
100m effective range @ 1 kHz
Voltages : 24vdc;115vac;230vac
DC version has reverse polarity protection.
A120D : IP67 A120E : IP66
Enclosure material : Marine grade LM6 Aluminium
Chromated & powder coated finish - good resistance to
hum idity and salt s pray environments.
BExA120 Horn : High impact UL94 V0 & 5VA FR ABS
BExDA120 Horn : Anti-Static High impact ABS
Operating temperature : -50 to +55°C
Storage temperature : -50 to +70°C
Large range of certified end of line resistors.
Weight : DC:3.20kg AC: 3.40kg
KEMA Certificate number : 99ATEX6312
BExA120D & BExA120E
Flameproof voice sounders Zones 1 & 2 ©N2GEExdllCT4 © II 2G EExde MC T4
BExDA120D & BExDA120E
Flameproof & Dust ignition proof
voice sounders
Zones 1, 2, 21 & 22
© II 2G/D EExd IIC T4 T100X
© II 2G/D EExde IIC T4 T100X
Installation Features.
• Very large termination area.
• Dual M20 ISO cable gland entries (supplied with one stopping plug).
• Ratchet adjustable stainless steel 'IT bracket for positive adjustment under harsh conditions.
• IN & OUT terminals
• Terminals accept 0.5 to 4.0mm2 cables.
• Line monitoring : Min. 500 Ohm 2w, or 3k3 Ohm 0.5w resistor, or diode within EExd enclosure (dc versions)
The sounder records, stores and plays back user defined messages stored directly to non-volatile memory without any intermediate analogue to digital conversion.
A single 16 second, message may be recorded and played back with a choice of 1 of 10 user selectable alarm tones (including silence to allow speech only option).
Input voltages and current consumption for the A120D & A120E voice sounders:
24vdc
115vac
230vac
50/60Hz
50/60Hz
+/-25%
+/-10%
+/-10%
480 mA
90mA
45mA
Voltage :
Voltage range : Current mA :
A120D unit :
_
A120D unit :
A120E unit :
27500
A120E unit :
Also available :
• BEx(D)S110 & S120 EEx d & EEx de sounder • units with output levels of 117dB(A)
• Programmable versions with 45 • tones and 4 stages.
BEx(D)L15 & 25 watt EEx d & EEx de loudspeakers.
BEx(D)TS110 & BExTB G05 EEx d Telephone ringers and beacons.
BEx(D)A110 EEx d & EEx de Voice Annunciation units. BExBG EEx d & EEx de 5, 10 & 15 Joule Xenon beacons
Page 1 of 2
European Safety Systems Impress House Mansell Road London, U.K. W3 7QH
Tel : +44 (0) 20 8743 8880
Fax : +44 (0) 20 8740 4200
mail : sales@e2s.com
Ltd
web : www.e2s.com
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
pdf-page pdf di En 2008-12-49-05