You may also be interested in
Isolator, Magnetic switch, Digital controller, Speed sensor, Electrical enclosure
Text version of the page
Thermal-Magnetic Circuit Breaker 201/-WA
Issue C www.e-t-a.com 2 - 7
2
Current Internal resistance (Ù) Current Internal resistance (Ù)
rating (A) 201 201-WA rating (A) 201 201-WA
0.05 447 211 3 0.19 0.054
0.1 131 48 4 0.090 0.035
0.2 40 12.4 5 0.061 0.025
0.3 19.3 5.7 6 0.041 100 MÙ (DC 500 V)
Interrupting capacity Icn 201 201-WA
0.05...0.8 A 0.05...0.2 A self-limiting
1...2 A 0.3...2 A 200 A
2.5...16 A 2.5...10 A 400 A
Interrupting capacity
(UL 1077) IN UN
0.05...16 A AC 250 V 1,000 A
0.05...16 A DC 80 V 1,000 A
Degree of protection operating area IP40
(IEC 60529/DIN 40050) terminal area IP20
Vibration 5 g (57-500 Hz), ± 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock 25 g (11 ms)
to IEC 60068-2-27, test Ea
Corrosion 96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH
to IEC 60068-2-78, test Cab
Mass approx. 60 g
Authority Voltage ratings Current ratings
VDE (EN 60 934) AC 240 V; DC 65 V 0.05...16 A
CSA, UL AC 250 V; DC 80 V 0.05...16 A
UL (only type 201) DC 65 V 0.05...25 A
Standard current ratings and typical internal resistance values
Type No.
201 single pole, rail mounted version
201-WA low-resistance version
Option
2705 fitted with adapter X 200 409 01
Current ratings
0.05...16 A (type 201)
0.05...10 A (type 201-WA)
201 - .. - .... - 10 A ordering example
The exact part number required can be built up from the table of choices shown
above. Ordering references for optional features should be omitted if not required.
|
|