video corpo

PC10PN
4Pages

{{requestButtons}}

Catalog excerpts

PC10PN - 1

Description The bus controller CPC10xx-Tx is the central communication sub-assembly of the intelligent power distribution systems type ControlPlex®. The CPC10 allows communication with up to ninety-six electronic circuit protectors ESX50D-S1xx. It enables read-out of the electronic circuit protectors' status, their corresponding operation data such as the present load current and the load voltage and it enables control and parameterising of the devices. In addition the CPC10 ensures the connection between the circuit protectors and superordinate control level by means of the integral field bus interface. Its internal ELBus® interface allows realisation of the connection to the power distribution boards and the plugged-in electronic circuit protectors type ESX50D-S. The number of ELBus® interfaces can be selected for two different versions. The bus controller CPC10xx-T1 can be used with one ELBus® interface, the bus controller CPC10xx-T4 can be used with four ELBus® interfaces. The selection of the corresponding bus controller depends on the required system expansion stage and offers the customer the choice between the connection of one to four power distribution boards and thus the possibility to communicate with up to 24 or even 96 electronic circuit protectors type ESX50D-S. The CPC10 enables the complete access to all requested parameters of the electronic circuit protector, its control and the visualisation of its status data. This is made available at the field bus interface for the superordinate control unit and also at the USB service interface for the operation on site. The combination of the bus controller CPC10 with the power distribution board SVS201-PWR-xx and the plugged in electronic circuit protectors ESX50D-S1xx offers a fully parameterisable protection of the DC 24 V circuits and ensures the selective overcurrent protection of sensors and actuators, of decentralised peripheral sub-assemblies etc. and their supply cables. It is therefore ideally suited to the use in machine construction and process control, in the chemical, pharmaceutical and foodstuffs industry, in building automation, steel production and car manufacturing. ControlPlex® reduces wiring time, increases system availability and enhances diagnostic functions. Suitable for the following types: Distribution rails SVS201-PWR-xx Electronic circuit protector ESX50D-S100 (completely parameterisable by means of the CPC10) Electronic circuit protector ESX50D-S110 (current rating adjustable by means of the rotary switch on the circuit protector, otherwise completely parameterisable via the CPC10) • Integral DC 24 V power distribution system for power distribution and overcurrent protection • Complete diagnosis and parameterising of the entire power distribution system • For electronic circuit protectors ESX50D-S100 / -S110 • Variable configuration of the connection with up to 96 electronic circuit protectors • Fully featured communication interfaces such as PROFIBUS-DP, PROFINET etc. • Service and maintenance interface via USB terminal • Integral memory HISTOMEMO for overload and short-circuit diagnosis of the load circuits • Profitability through considerably reduced wiring time • Reduction of planning, design and installation time • Ease of maintenance, diagnosis and system extension Application: Intelligent DC 24 V Power Distribution Systems Line entry load module (X41) Rated voltage DC 24 V (18 ... 32 V) Current rating typically 60 mA Terminals 4 x screw terminals, (+/+/0V/0V) cable cross section max. 2.5 mm2 flexible with wire end ferrule (with plastic sleeve) 0.25 - 1.5 mm2 flexible with wire end ferrule (without plastic sleeve) 0.25 - 2.5 mm2 stripping length 7 mm ELBus® termination to connect the power distribution boards (-X51, -X52, -X53, -X54) X51 COM-1: connection for the first power distribution boards SVS201-PWR-xx cable length max. 2m typically H07V-K 1.5 mm2 female connector 1: Data line ELBus® ELB female connector 2: ELBus® DC +24V female connector 3: ELBus® GND only with CPC10PN-T4 X52 COM-2: connection for the second power distribution board SVS201-PWR-xx cable length max. 2m typically H07V-K 1.5 mm2 female connector 1: Data line ELBus® ELB female connector 2: ELBus® DC +24V female connector 3: ELBus® GND only with CPC10PN-T4 X53 COM-3: connection for the third power distribution board SVS201-PWR-xx cable length max. 2m typically H07V-K 1.5 mm2 female connector 1: Data line ELBus® ELB female connector 2: ELBus® DC +24V female connector 3: ELBus® GND only with CPC10PN-T4 X54 COM-4: connection for the fourth power distribution board SVS201-PWR-xx cable length max. 2m typically H07V-K 1.5 mm2 female connector 1: Data line ELBus® ELB female connector 2: ELBus® DC +24V female connector 3: ELBus® GND

Open the catalog to page 1
PC10PN - 2

USB service and maintenance interface (-X61) X61 connection to a PC for communication with the user software cable length max. 2.5 m Type: USB-2.0 Type B PROFINET interface (-X81, -X82) with integral switch X81 Connection to bus system PROFINET Type: RJ45 When wiring and connecting to the bus system PROFINET the installation and wiring regulations of the PROFIBUS User Organisation (PNO) have to be observed. X82 Connection to bus system PROFINET Type: RJ45 When wiring and connecting to the bus system PROFINET the installation and wiring regulations of the PROFIBUS User Organisation...

Open the catalog to page 2
PC10PN - 3

Bus Controller CPC10PN (ControlPlex®) Notes for installation T he CPC10 is only intended for use with safety extra-low voltage (=24 V DC). C onnection to a higher or not reliably disconnected voltage can cause hazardous conditions or damages. O nly the intended power distribution boards must be used. T he technical data of the used circuit protectors have to be observed. The entire power distribution system must only be installed by qualified personnel. Only after expert installation must the device be supplied with power. A fter tripping of the circuit protector and before reset, the cause...

Open the catalog to page 3

All E-T-A catalogs and technical brochures

  1. MPR10, MPR20

    5 Pages

  2. CATALOGUE

    108 Pages

  3. CPC20

    12 Pages

  4. CPC12

    8 Pages

  5. REX12

    16 Pages

  6. PC10IO

    2 Pages

  7. PC10PB

    4 Pages

  8. SVS18

    6 Pages

  9. 1140-E

    4 Pages

  10. 1110

    2 Pages

  11. 129-L11-H-KF

    2 Pages

  12. 127

    4 Pages

  13. 104

    4 Pages