Description
Capacitive Level Sensor NR160 is designed to monitor liquids andpowders with high relative dielectric constant
ε
r . With MIN/MAXselector switch.The functions for MIN or MAX monitoring as well as other properties
(output signal LSS or HSS, response delay etc.) are factory pre-set.
The switch point is adjustable by means of a teach-in momentary
switch.
Features
● status indication by 2 LEDs
● max. medium temperature +130 C
● min/max selector switch
NR160-...
● transistor output
● recommended for granules, powder, water and other electricallyconductive media
Technical data
2
Ordering information
Input voltageDC 9...36 V or with power supply NG03
Type >
Power consumptiontypically 17 mAoutputtransistor, plus switching (HSS) or minus switching (LSS)max.load1.0 A cont. duty at max. 125 C and 24 V DC
1.0 A cont. duty at max. 105 C and 32 V DC
1.5 A short-time overload, power LED blinking, short circuit and overload proof,
NR160 level sensor for water and media with low electrical conductivity Voltage rating U2 DC 9...36 V Medium W water S special medium Mounting method 02 G3/4A thread to DIN 13, part. 6, ISO 228/1 04 3/4 >
"
NPT thread to ANSI B1.20.1 >
with integral free-wheeling diode
Function A Minimum OC (open circuit principle) >
Voltage drop < 200 mV
B Maximum OC (open circuit principle) >
Ambient temperature -20 C...+125 CMedium temperature -20 C...+125 C, for a short period
C Minimum RC (closed circuit principle) D Maximum RC (closed circuit principle) >
(1 minute) up to 150C
output signal L LSS minus switching >
Response delay typically 500 ms
Switching point hysteresishorizontally mounted:
H HSS plus switching Self test function >
(depending on medium viscosity) 21.8 mm max. (probe dia.)
without 1 1 second >
Reverse polarity protectionfitted between plus and minus pole
Degree of protection IP68 housing
2 2 seconds Response delay >
to IEC 529/DIN 40050
00 without >
02 2 seconds 03 3 seconds >
Pressure resistance 25 bar/367.5 PSI
07 7 seconds >
Connection screw terminals max. 1 mm
2 (AWG 18)Material probePA12-Gf30fitting, AdapterV4A, DIN 1.4571/AISI 316 Tisealing (O ring)EPDM70, black, interlaced peroxide
17 17 seconds Fitting material 2 stainless steel V4A-DIN 1.4571 Connection A with cable gland and cable >
1) E12 connector M12x1, 3-pole >
housing coverPA6-3-T Material spec.PA12-Gf30 = Polyamide with glass fibre 30%
(standard) >
2) NR160 -U2W02AH000 - 2A ordering example >
PA6-3-T = Trogamide, transparentVibration 10 Hz...57 Hz 0.765 mm(sinusoidal)57 Hz...2 000 Hz 10 g
1) cable type 20: see accessories >
Extension:
2) suitable connecting cable: Do + Ka type 24: see accessories >
Adapter X 222 789 01 is available as an extension for use as
immersion sensor in wells and sewage plants. (IEC 60068-2-6)Shock50 g/11 ms
Accessories
(IEC 60068-2-27)EMC requirementsinterference: EN 61000-6-3/4 (EMC directive, CE logo)interference: EN 61000-6-2 Mounting method screw in Mounting attitude optionalCable length200 m max. (AWG 24) Observe voltage drop!Massplug version: 188 g
Options
cable version: 258 g (with 2 m cable) AC voltage ratings and relay outputs: only with power supply NG03 (see technical data NG03)
mark to demonstrate compliance with applicable directive. Issue A www.e-t-a.com 2 - 23