www.e-t-a.com
Electronic Circuit Breaker ESS20-0..
Issue C 5 - 7
5
Description
Electronic circuit breaker type ESS20-0.. is designed to ensure
selective disconnection of individual loads in systems which are
powered by a DC 24 V switch-mode power supply.
DC 24 V power supplies, which are widely used in industry today, will
shut down the output in the event of an overload with the result that
one faulty load in the system can lead to complete disconnection of
all loads. As well as an unidentified failure this also means stoppage
of the whole system.
Through selective disconnection the ESS20-0.. responds much
faster to overload or short circuit conditions than the switch-mode
power supply. This is achieved by a combination of active current
limitation and well-proven circuit breaker technology including
physical isolation. The ESS20-0.. limits the highest possible current
to 1.8 or 1.5 times the selected rated current of the circuit breaker.
Thus it is possible to switch on capacitive loads of up to 20,000 F
lamp loads, but they are disconnected only in the event of an overload
or short circuit.
For optimal adjustment to the application conditions the current rating
of the ESS20-0.. can be selected in fixed values from 0.5 A...10 A and
in adjustable variants 1 A/2 A or 3 A/6 A. Failure and status indication
are provided by a bicolour LED and an integral signal contact.
The ESS20-0.. features a width of only 12.5 mm and can be plugged
into the E-T-A power distribution socket Module 17plus and SVS02/
SVS04 (for ESS20-003) ensuring ease of installation and saving space
in control cabinets.
Features
Approvals
Selective load protection with physical isolation in the event of a fault.
All types of loads can be connected (small DC motors etc. on
request).
Active current limitation (1.8 or 1.5 times rated current IN = 8 A or
10 A) for safe connection of capacitive loads up to 20,000 F and
on overload/short circuit.
Electronic trip characteristic.
Reliable overload disconnection with 1.1 x IN plus, even with long
load lines or small cable cross sections (see table 2).
Selectable current ratings (fixed values 0.5 A...10 A or two steps:
1 A/2 A or 3 A/6 A).
Manual ON/OFF button (push-push actuation).
Clear status and failure indication.
Width per unit only 12.5 mm.
Plug-in mounting utilising power distribution system Module 17plus
or SVS02/SVS04 ( for ESS20-003), see product group 7.
ESS20-0..
Technical data (Tambient = 25 C, operating voltage US = DC 24 V)
Authority Voltage rating Current ratings
UL 1077 DC 24 V 0.5...10 A
Attention: the user has to make sure that the cable cross sections
of the relevant load circuit are suitable for the current rating of the
ESS20 used.
Operating data
Operating voltage US DC 24 V (18...32 V)
Current rating IN fixed current ratings: 0.5 A, 1 A, 2 A, 3 A,
4 A, 6 A, 8 A, 10 A
switchable: 1 A/2 A or 3 A/6 A
Power consumption typically 13 mA
Trip current (bimetal) typically 0.3 A
(only in the event of a failure, before physical isolation)
Status indication bicolour LED:
by means of GREEN: unit is ON, power-MOSFET is
switched on
ORANGE: in the event of overload or
short circuit until physical isolation
LED not lighted: push button in OFF
position
potential-free signal contact (changeover
contact)
OFF-position of push button
Reverse polarity internal bimetal (fail-safe element) trips,
protection of US push button moves into OFF position
Load circuit
Load output Power-MOSFET switching output
(high side switch)
Max. data of load
with side-by-side mounting see table 1
Voltage drop at IN see table 1
Overload disconnection typically 1.1 x IN (1.05...1.35 x IN)
Short-circuit current IK typically 1.8 x IN / active current
limitation
Trip time see time/current characteristics
for physical isolation typically 5 sec at Iload > 1.1 x IN
for electronic disconnection typically 5 sec...100 ms at Iload > 1.8 x IN
or 1.5 x IN
Temperature disconnection internal temperature monitoring with
physical isolation
Low voltage monitoring
load output ON at US >16 V
OFF at US < 8 V
Starting delay tstart typically 0.3 sec after every switch-on
and after applying US
Disconnection of load circuit single pole (switch contact)
- by push-push actuation of the blue
push button
- upon electronic fault disconnection
(overload, short circuit)
- with reverse polarity
Free-wheeling circuit external free-wheeling diode
recommended with inductive load
Several load outputs must not be connected in parallel.
|
|