M5300
2Pages

{{requestButtons}}

Catalog excerpts

M5300 - 1

M5300 M5300 Sweep Frequency Response Analyzer (SFRA) ® A tool for detecting “hidden” transformer faults The M5300 detects mechanical failure or movement of windings due to short circuits, mechanical stresses or transportation. Use it to ensure transformer performance, reduce maintenance cost, and increase the service life of transformers. A major advance in transformer condition analysis. M5300 Sweep Frequency Response Analyzer (SFRA) For Transformer Core & Winding Movement Diagnosis. Comes with built in PC. The M5300 uses Sweep Frequency Response Analysis, a proven technique for making accurate and repeatable measurements. Pioneered by Doble the sweep approach has become the industry standard and is the preferred method for making frequency domain measurements. Here’s how SFRA works: The M5300 sends an excitation signal into the transformer and measures the returning signals across a broad frequency range. By comparing this response to baseline and other results (such as from similar units), you can identify deviations and confirm internal mechanical problems. DIAGNOSE problems early. PREVENT expensive equipment failures. Take CONTROL. Why wait for problems to develop? With the M5300’s non-intrusive test technique, you can test your power apparatus any time you suspect a problem. Or just use it as part of your regular maintenance program. Either way, you identify problems before they lead to failure, such as: • Core movement • Winding deformation and displacement • Faulty core grounds • Partial winding collapse • Hoop buckling • Broken or loosened clamping structures • Shorted turns and open windings

Open the catalog to page 1
M5300 - 2

M5300 SFRA Technical Specifications Excitation Source: Channels: 1 Frequency Range: 10 Hz – 25 MHz Output Voltage: V peak-to-peak at 20 50 Ohms Output Protection: Short circuit protected Source Impedance: Ohms 50 Calibration Interval: years 3 Measurement Channels: Channels: 2 Sampling: Simultaneous Frequency Range: 10 Hz – 25 MHz Max. Sampling rate: 100 MS/s Input Impedance: Ohms 50 Physical Specifications: Dimensions: 1 0.0 H x 16.0 W x 15.5 D in 25.4 H x 40.6 W x 39.4 D cm Weight: 22.5 lbs (10.2 kg) Power Supply: The M5300 comes with a carrying strap for easy transportation 100-240V AC...

Open the catalog to page 2

All Doble Engineering catalogs and technical brochures

  1. F6816

    2 Pages

  2. IDD series

    2 Pages

  3. DOMINO

    4 Pages

  4. DFA100

    2 Pages

  5. M5400

    2 Pages

  6. F5814

    4 Pages

  7. TDR900

    2 Pages

  8. TDR9000

    4 Pages

  9. TDR9100

    2 Pages