| | | Type DCP2 | | |
| | | |
| | | Technical specifications, cont. | | |
| | | |
| | | DCP2-2440: Primary max. 2.5 mm2 Secondary 10.0 mm2 Green LED - operating indication | | |
| | | DCP2-XX05 DCP2-XX10 and -2410/115V DCP2-2420 DCP2-2420 DCP2-2440 | | >80 ms at Um = 230V AC >15 ms at Um = 230V AC >15 ms at Um = 230V AC >5 ms at Um = 400V AC >5 ms at Um = 400V AC | | |
| | | Hold-up time: | | |
| | | |
| | | Indication: Housing: Materials: | | |
| | | |
| | | |
| | | |
| | | All plastic parts are self-extinguishing to UL94 (V0) DCP2-2440 is encapsulated in a metal housing 147 x 123 x 86 mm (DCP2-1205, -2405) 205 x 123 x 86 mm (DCP2-1210, -2410, -2410/115V) 240 x 153 x 86 mm (DCP2-2420) 292 x 185 x 130 mm (DCP2-2440) DIN-rail, EN 50022-35 | | |
| | | The determined time, during which a power supply/charger's output remains within a specified voltage range after its input ceases EN 61000-6-3 EN 61000-6-4 EN 61000-6-1 EN 61000-6-2 EN 61000-6-5 | | |
| | | |
| | | Dimensions: W x H x D | | |
| | | EMC: | | |
| | | |
| | | |
| | | |
| | | Mounting: | | |
| | | RFI suppression: | | |
| | | |
| | | |
| | | According to VDE0875 T11/EN55011 class B | | |
| | | |
| | | |
| | | Static discharge ESD: IEC 1000-4-2: Electromagnetic fields: Burst IEC 1000-4-4: | | |
| | | 8kV contact discharge 15kV free air discharge 10V/m according to IEC 1000-4-3 | | |
| | | |
| | | 4kV input 2kV output AC-coupled 4kV asymmetrical 4kV symmetrical | | |
| | | |
| | | Surge IEC 1000-4-5: | | |
| | | Distance for convection: | | |
| | | |
| | | | | | | | | | 100 mm above and below the DCP2 | | | | 30 mm to each side | | | | | DCP2-1205 | 0.8 kg | | | | DCP2-2405 | 0.8 kg | | | | DCP2-1210 | 1.2 kg | | | | DCP2-2410 | 1.2 kg | | | | DCP2-2410/115V | 1.2 kg | | | | DCP2-2420 | 1.9 kg | | | | DCP2-2440 | 3.6 kg | | | | | | | | | |
| | | |
| | | |
| | | Galvanic separation: | | |
| | | Between AC voltage, output and protective earth (PE): 3.11kV DC between terminals Prim./Sec. 3.11kV DC between terminals Prim./PE 0.78kV DC between terminals Sec./PE VDE0805/EN60950/IEC950/EN61010-1 Class I IP20 <0.75mA (47-63Hz line frequency) (DCP2-2420 3 phase supply and DCP2-2440 <3.5mA) -10...70°C (operating, free convection) -25...85°C (storage) 2.5%/K above +60°C DCP2-1205, -1210, -2405, -2410 and -2410/115V: Primary max. 2.5 mm2 Secondary 2.5 mm2 DCP2-2420: Primary max. 2.5 mm2 Secondary 4.0 mm2 | | |
| | | Weight: | | |
| | | |
| | | |
| | | Safety: Protection: Deg. of protection: Leakage current: Temperature: Reduction of output power: Terminals: | | |
| | | |
| | | Order specifications | | |
| | | |
| | | Type - output voltage - output current - supply Example: DCP2 - 24V DC - 5A DC - 1 x 230V AC | | |
| | | |
| | | Due to our continuous development we reserve the right to supply equipment which may vary from the described. | | |
| | | |
| | | |