ventilation unit - 12 / 36 Pages

SPECIFICATIONS
VAM-FA8
Ventilation
VAM 8 0 0 FA
VAM-FA
150
250
350
500
650
800
1000
1500
2000
Temperature exchange efficiency (%)
ultra-high
74
72
75
74
74
74
75
75
75
high
74
72
75
74
74
74
75
75
75
low
79
77
80
77
77
76
76.5
78
78
Enthalpy exchange efficiency (%)
for heating
ultra-high
64
64
65
62
63
65
66
66
66
high
64
64
65
62
63
65
66
66
66
low
69
68
70
67
66
67
68
68
70
for cooling
ultra-high
58
58
61
58
58
60
61
61
61
high
58
58
61
58
58
60
61
61
61
low
64
62
67
63
63
62
63
64
66
Power supply
VE
1 ~, 220~240V, 50Hz
Sound pressure level dB(A)
heat exchange mode
ultra-high
27-28.5
28-29
32-34
33-34.5
34.5-35.5
36-37
36-37
39.5-41.5
40-42.5
high
26-27.5
26-27
31.5-33
31.5-33
33-34
34.5-36
35-36
38-39
38-41
low
20.5-21.5
21-22
23.5-26
24.5-26.5
27-28
31-32
31-32
34-36
35-37
bypass mode
ultra-high
27-28.5
28-29
32-34
33.5-34.5
34.5-35.5
36-37
36-37
40.5-41.5
40-42.5
high
26.5-27.5
27-28
31-32.5
32.5-33.5
34-35
34.5-36
35.5-36
38-39
38-41
low
20.5-21.5
21-22
24.5-26.5
25.5-27.5
27-28.5
31-33
31-32
33.5-36
35-37
Casing
Galvanised steel plate
Insulation material
Self-extinguishable urethane foam
Dimensions H xWxD
mm
269 x 760 x 509 285 x 812 x 800
348 x 988 x 852
348x988x1,140
710x1,498x852
10x1,498x1,140
Weight
kg
24 33
48
61
132
158
Heat exchange system
Air to air cross flow total heat (sensible heat + latent heat) exchange
Heat exchange element material
Specially processed non-flammable paper
Air filter
Multidirectional fibrous fleeces
Fan
type
Sirroco fan
air flow rate (nWh)
ultra-high
150
250
350
500
650
800
1,000
1,500
2,000
high
150
250
350
500
650
800
1,000
1,500
2,000
low
110
155
230
350
500
670
870
1,200
1,400
external static pressure (Pa)
ultra-high
69
64
98
98
93
137
157
137
137
high
39
39
70
54
39
98
98
98
78
low
20
20
25
25
25
49
78
49
59
Motor output
kW
0.030 x 2 0.09
) x 2 0.14
0 x 2
0.230 x 2
0.230 x 4
Connection duct diameter
mm
0 100 | 0 150 | 0 200
0 250
0 350
-15°C ~ +50°CDB, 80% RH or less
Unit ambient condition
Notes:
> Air flow rate can be changed over to low mode or high mode.
> Sound pressure level is measured at 1.5m below the center of the body.
> Sound pressure level is measured in an anechoic chamber.
> Sound pressure levels generally become higher than this value depending on the operating conditions, reflected sound, and peripheral noise.
> The sound pressure level at the air discharge port is about 8dB higher than the unit's sound level.
> Even when the outdoor temperature is below -15°C, the system is operable down to -20°C with the preheater installed at the outdoor air intake side.
12
ventilation unit
  1. P. 1

  2. P. 7

    Automatic Changeover to Efficient Operation Patterns Operation automatically switches to the optimum pattern to suit prevailing conditions Cooling...
  3. P. 8

    > Simple Design and Construction The unit can be installed either horizontally or upside down in accordance with the conditions of the location....
  4. P. 9

    3. CLEAN AIR Fresh-Up Operation The user can select between 2 fresh-up modes via the remote control. 1. Supply rich mode: Raising the air...
  5. P. 10

    VKM FEATURES Exhaust Fan Heat Exchanger Elements Damper Motor (Exhaust air to outdours) DX coil (Direct expansion coil)...
  6. P. 11

    Efficient Outdoor Air Introduction with Heat Exchanger and Cooling/Heating Operation Indoor unit with outdoor air treatment. The temperature can be...
  7. P. 12

  8. P. 13

    Ventilation, DX coil & humidifier VKM80-100GAM VKM50GAM VKM80GAM VKM100GAM DX coil capacity cooling kW 4.71...
  9. P. 14

    Ventilation & DX coil VKM80-100GA VKM50GA VKM80GA VKM100GA DX coil capacity cooling kw 4.71 7.46 9.12 ...
  10. P. 15

    OPTIONS wiring adapter for electrical appendices KRP2A61 for humidifier (running ON signal output) KRP50-2 for heater control kit...
  11. P. 16

    1. PC BOARD ADAPTER FOR HEATER CONTROL KIT - BRP4A50 When the installation of an electric heater is required in a cold region, this adapter with...
  12. P. 17

    Silencer Duct adapter Description VAM150FA VAM250FA VAM350FA High efficiency filter YAFM323F15 YAFM323F25 YAFM323F35...
  13. P. 18

  14. P. 19

  15. P. 20

  16. P. 30

Text version

All DAIKIN Europe catalogues and technical brochures

  1. EZC-1

    14 Pages

    En

Archived catalogues

  1. Conveni-pack

    12 Pages

    En
  2. Chillers

    140 Pages

    En
  3. air purifier

    12 Pages

    En