The modular Conveni-pack concept allows a wide and flexible range of installation practice to suit the variety of
conditions met on-site:
• Configurations: multiple outdoor units can be positioned to make the best use of the space available, in
blocks, rows or distributed around the building to minimize pipe runs.
• Distance: the length of piping between the outdoor unit and the furthest refrigeration cabinet or air
conditioning unit on the circuit can be up to 100m.
• Height: the outdoor unit can be placed up to 30m above the lowest or up to 5m below the highest
refrigeration cabinet or air conditioning unit.
• Inside the building: sufficient air flow around the unit must be provided.
2.33 m (2 units)
1.75 m (1 unit)
3 m (2 units)
A
A
A
A
A
A
A A
1.48 m (1 unit)
1.48 m (1 unit)
2.86 m (2 units)
1.75 m
4.24 m (3 units)
Up to 30m
above cabinets
Up to 5m below the
air conditioning units
Up to 100m from
furthest indoor unit
Blocks Rows Distributed
The technology of Conveni-pack closely resembles
VRV which has been installed in residential and noise
sensitive areas over many years. Noise is minimized
by:
• The continuous gas flow of the scroll compressors
which is significantly quieter than the pulsating
flows of a reciprocating compressor, and the
inverter driven compressor allows partial load
operation, which is quieter than conventional
on-off systems.
• Compressors with specially designed sound
suppressing jackets.
• Aero-spiral fan blades combined with aerodynamic
grilles that reduce turbulence and noise. All fans
have inverter driven motors that provide the right
air volumes without sudden noise changes.
Conveni-pack features a programmable night
setback mode that reduces noise by limiting the fan
speed at sensitive times of the day.
Shop
B B B B
B
B B
A = 0.5 m / B = 0.1 m - These minimum distances must be respected.
The Conveni-pack outdoor unit has a footprint of 1.28m x 0.75m.
General constraints in height and pipe length must be respected.
A
Configuration and Installation Flexibility
Low Noise
Shop Shop Carpark
|
|