2. SPECIFICATIONS & ACCESSORIES
FXFQ-P
Roundflow ceiling mounted cassette
SPECIFICAT
FXFQ-P
Capacity
ONS
20 25 32 40 50
63
80 I 100 125
cooling
kW
2.2 2.8 3.6
4.5
5.6
7.1
9.0
11.2
14.0
heating
kW
2.5 3.2 4.0
5.0
6.3
8.0
10.0
12.5
16.0
Powerinput
cooling
kW
0.053
0.063
0.083
0.095
0.120
0.173
0.258
heating
kW
0.045
0.055
0.067
0.114
0.108
0.176
0.246
Dimensions
(HxWxD)
mm
204x840x840
246x840x840
288x840x840
Weight
unit
kg
20.0 | 21.0
24.0
26.0
Casing
Galvanised steel
Air Flow Rate
cooling
high/low
m3/mln
12.5/9.0
13.5/9.0
15.5/10.0
16.5/11.0
23.5/14.5
26.5/17.0
33.0/20.0
heating
high/low
m3/min
12.5/9.0
13.5/9.0
15.0/9.5
17.5/12.0
23.5/14.5
28.0/17.5
33.0/20.0
Sound power (nominal)
cooling
dB(A)
49
50
51
52
55
58
61
Sound pressure
cooling
high/low
dB(A)
31/28
32/28
33/28
34/29
38/32
41/33
44/34
heating
high/low
dB(A)
31/28
32/28
33/28
36/30
38/32
42/34
44/34
Refrigerant
name
R-410A
Power Supply
1~/220-240V/50Hz
Piping Connections | L/G/D | diameter | mm
635/12.7/32 | 6.4/ 12.7/32 9.5/ 15.9/32
Air Filter
Resin net with mold resistance
Drain-up Height | mm
750
Decoration Panel
model
BYCQ140CW1
colour
RAL9010
(HxWxD 1 mm
50x950x950
weight 1 kg
5.5
Notes:
The sound pressure values are mentioned for a unit installed with rear suction
The sound power level is an absolute value indicating the power wich a sound source generates.
Nominal cooling capacities are based on: indoor temperature: 270CDB, 190CWB, outdoor temperature: 350CDB, equivalent refrigerant piping: 5m, level difference: Om. Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: Om. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
ACCESSORIES
FXFQ-P
20 I 25 I 32 I 40 I 50 I 63 I 80 I 125
Wired remote control
BRC1D52
Infrared remote control
cooling only
BRC7F533F
heat pump
BRC7F532F
Decoration panel
BYCQ140CW1
Replacement long life filter (non-woven type)
KAFP551K160
Fresh air intake kit (20% fresh air Intake) (chamber type)
KDDQ5C140
Air discharge outlet sealing member
KDBHQ55C140