Configuration and Installation Flexibility

The modular Conveni-pack concept allows a wide and flexible range of installation practice to suit the varietyof conditions met on-site:• Configurations: multiple outdoor units can be positioned to make the best use of the space available,in blocks, rows or distributed around the building to minimize pipe runs.• Distance: the length of piping between the outdoor unit and the furthest refrigeration cabinet or air conditioning unit on the circuit can be up to 100m. • Height: the outdoor unit can be placed up to 30m above the lowest or up to 5m below the highestrefrigeration cabinet or air conditioning unit.• Inside the building: sufficient air flow around the unit must be provided.
BlocksRowsDistributed 2.33 m (2 units) 4.24 m (3 units)Up to 30m above cabinets Up to 5m below theair conditioning units AAAAAAAA 1.48 m (1 unit)1.48 m (1 unit)2.86 m (2 units) A Shop BBBBBBB Up to 100m from furthest indoor unit 1.75 m 1.75 m (1 unit)3 m (2 units) ShopShop Carpark A = 0.5 m / B = 0.1 m - These minimum distances must be respected.The Conveni-pack outdoor unit has a footprint of 1.28m x 0.75m. General constraints in height and pipe length must be respected.

Low Noise

The technology of Conveni-pack closely resemblesVRV which has been installed in residential and noise sensitive areas over many years. Noise is minimized by:•The continuous gas flow of the scrollcompressors which is significantly quieter than the pulsating flows of a reciprocating compressor, and the inverter driven compressor allows partial load operation, which is quieter than conventional on-off systems.•Compressors with specially designed soundsuppressing jackets. •Aero-spiral fan blades combined withaerodynamic grilles that reduce turbulence and noise. All fans have inverter driven motors that provide the right air volumes without sudden noise changes. Conveni-pack features a programmable night setback mode that reduces noise by limiting the fan speed at sensitive times of the day. 9 9

pageCatalog pdf di En 2012-05-22-29