INSULATION MONITORING
VERSIONS FOR NETWORKS ac MAX 500 V STRONGLY DISTORTED
WITH HARMONIC COMPONENTS AND/OR DIRECT-CURRENT COMPONENTS
GENERAL
These devices allow insulation monitoring on earth of electrical networks in alternating till 500 V A.C. isolated (IT systems). Measure's technique adopted is particular because measure's signal is codified and varying. This works in order to let a right measure of insu­lation independently from under-control network. The presence in the network of strong distortions with high harmonic components (sub harmonic) and direct-current components could cause measure's problems to others techniques. This solution allow device's use.
RI-R50 in network with rectifiers, power's electronics, variable-speed drive and so on...Surveying leakage current to earth it's possible to measure insulation level.
RI-R50 have a large amount of programming possibilities with frontal button and digital display three-digit for visualising measuring and pro­gramming parameters.
In output there is a relay output voltage-free with functions adjustable. Optionally, there is also a serial output RS485 for bidirectional commu­nication with a professional monitoring system (MANUFACTURERS OF PLC, PC and so on). Communication's protocol used is MODUBUS-RTU.
MODELLI
RI-R50 Vaux: 230 V 50-60 Hz (standard version) RI-R50 Vaux: 115 V 50-60 Hz (optional version)
FUNCTIONS AND OPERATORS - LEGENDA
3 4 5
Display for visualising under-control parameters' degree and for visualising settings
green LED SET for indication of device's programming status
yellow LED ALARM for indication alarm for out-threshold parameter's degree
red LED OUTPUT RELAY for indication status of output auxiliary relay
red LED ERROR/LINK FAIL for indication internal failure's alarm, lacked connection of under-control network
red LED R for indication visualisation of insulation's resistance parameter (kohm); flashing indication for out-threshold parameter
red LED Z for indication visualisation of insulation's impedance parameter; flashing indication for out-threshold parameter
+/- buttons UP/DOWN for selecting visualisation's parameter, for adjusting device's settings and for visualisation of max and min memorized degrees
RESET / SET button for access to device's programming, for alarm stop and for memorized degrees' reset
10 TEST / ENTER button for testing the device and remote signalling panels and for confirming SETUP settings
14
00000
0000
000000000
insu ation moritor RI-R50
SET
ALARM OUTPUT ERROR/ RELAY LINK FAIL
6
I R [kQ] i Z [kQ]
MIN/ MAX
[gjIC^ IresetìItestI
[■ + ■] r^^» [■SE^J [lENTERy
7
000000000 0
00000000