Catalogue INSULATION MONITORING
www.contrel.it
print switch display
Page / 2
Contrel elettronica - 94372
/ 2
See other catalogues for Contrel elettronica
Text version of the page
RI-R4SN series
INSULATION MONITORING /ERSIONS FOR NETWORK ac/dc MAX 48 V
ELECTRIC CHARACTERISTICS
■ I
Auxiliary supply voltage
24 V or 48 V 50-60 Hz ± 20 % or dc ± 20 %
Self-consumption
3 VA MAX
Network voltage
24 48 Vac/dc +10 %
Measuring voltage
24 V MAX
Measuring current
0.5 mA MAX
Internal impedance
100 kohm
Tripping threshold
RI-R48 adjustable 10 50 kohm by potentiometer suppliers RI-R48N adjustable 10 60 kohm by micro switches RI-F48 fixed 10 kohm
Tripping late Signalling and operators Output
Working temperature
Storing temperature
Relative humidity
Insulation test
Assembling position
Connection type
Protection's degree
Mounting according with DIN 50022
Weight
Standard reference
about 1 second led ON - led TRIP
buttons TEST and RESET (only model RI-R48 / RI-R48N) relay switch contact NO-C-NC MAX 5 A 250 Vac
- 10 ...+ 60 °C
- 20 ...+ 70 °C < 90 %
3 kV 60 sec / 4 kv imp. 1,2 / 50 [is indifferent
by screw terminals - wire section MAX 4 mm2
IP 40 frontal with cap - IP 20 case
easy connection snap on DIN rail 35 mm / 3 modules of 17.5 mm
approximately 300 g
CEI-EN 61010-1 / CEI-EN 61557-8 / VDE0413 part.8 / CEI-EN 61326-1
WIRING DIAGRAMS - LEGENDA
AUXILIARY SUPPLY - TERMINALS 1-3
Auxiliary supply could be taken from under-control network.
RI-F48 / RI-R48 / RI-R48N
Vaux
5
INSULATION MONITORING - TERMINALS 1-9
Terminals have to be connected between under-control network and measure's referring earth.
Maximum voltage applicable between these terminals is 48 V
CONNECTION OUTPUT RELAY - TERMINALS 6-7-8
Connection for remote signal by relays with switch free from voltage, max 5 A 250 V on resistive load.
Eventual connection for automatic or remote RESET
(only for models RI-R48 and RI-R48N), connect a button NC
between terminals 4 and 10.
3 14
6
LU
8 19
10
AUX1
AUX2 RESET
TEST
OUT-NC OUT-C OUT-NO
IL.
RESET
PE
CARICO
+
-o-
Eventual connection for remote TEST
(only for models RI-R48 and RI-R48N), connect a button NO
between terminal 5 and earth's conductor PE
LINEA ISOLATA max 48Vca/cc
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics