BASremote
8Pages

{{requestButtons}}

Catalog excerpts

BASremote - 1

BAS Remote data SHEET BAS Remote — Versatile Building Automation Appliance The BAS Remote series provide the system integrator a flexible building block when integrating diverse building automation protocols or when expanding the number of points in a building automation system. By supporting open system protocols such as BACnet®, Modbus and Sedona Framework™ SOX, the BAS Remote series is easily adaptable. For small systems, it can operate stand-alone. For larger systems, it can communicate to supervisory controllers over Ethernet. Depending upon the model, the BAS Remote has the flexibility to provide the following: Versatile Control Device — remote I/O, router, gateway and controller • • • • • • • • • • Web-page configuration BACnet/IP Remote I/O Modbus TCP Remote I/O Modbus Serial to Modbus TCP Router Modbus Serial to BACnet/IP Gateway Modbus Master to Attached Modbus Slaves Powered by Sedona Framework Controller Power over Ethernet (PoE) Customisable webpages Web Services Flexible Input/Output — expandable by adding modules • • • • • • Six universal input/output points web-page configurable Two relay outputs Thermistors, voltage, current, contact closure and pulse inputs Voltage, current and relay outputs 2-wire Modbus Serial Expansion port 2-wire expansion port for up to three expansion I/O modules DS-BASR0000-BA0

Open the catalog to page 1
BASremote - 2

Data Sheet — BAS Remote BAS Remote Master – Versatile Web Appliance The BAS Remote Master provides the ultimate in flexibility. It can be used for expansion I/O at remote locations where an Ethernet connection exists. Its built-in router and gateway capabilities address unique integration needs where more than one communications protocol is involved. It can operate as a function block programmable controller with its resident Sedona Framework Virtual Machine. Powered by a Linux engine, the BAS Remote Master can operate as BACnet/IP and Modbus TCP remote I/O, Sedona Framework controller,...

Open the catalog to page 2
BASremote - 3

Data Sheet — BAS Remote Typical I/O Point Configuration Screen

Open the catalog to page 3
BASremote - 4

Data Sheet — BAS Remote Powered by Sedona Framework for Implementing Control The BAS Remote Master incorporates Sedona Virtual Machine (SVM) technology developed by Tridium and compatible with their Niagara Framework™. Using established Tridium tools such as Workbench, a system integrator can develop a control application using Workbench’s powerful drag-and-drop visual programming methodology. Once developed, the program remains stored in the BAS Remote Master and executes by way of the SVM. The application can run standalone in the BAS Remote Master or interact with a program in a Tridium...

Open the catalog to page 4
BASremote - 5

Data Sheet — BAS Remote BACnet Protocol Implementation Conformance (PIC) Statement Versatile Building Automation Applla BACnet Protocol Implementation Conformance Statement (Annex A)

Open the catalog to page 5
BASremote - 6

Data Sheet — BAS Remote Wiring Diagram Dimensions (for all models) DS-BASR0000-BA0 Page 6

Open the catalog to page 6
BASremote - 7

Data Sheet — BAS Remote Specifications Universal Inputs/Outputs (Channels 1–6) Configured As Characteristics Analog output Analog input Temperature input Contact closure input Pulse input 0–10 VDC or 0–20 mA scalable by user. 12-bit resolution. Maximum burden 750 Ohms when using current output. 0–10 VDC or 0–20 mA scalable by user. 10-bit resolution. Input impedance 100 kΩ on voltage and 250 Ω on current. Type II or type III thermistors +40°F to +110°F (+4.4°C to +44°C) Excitation current 2 mA. Open circuit voltage 24 VDC. Sensing threshold 0.3 VDC. Response time 20 ms. 0–10 VDC scalable by...

Open the catalog to page 7
BASremote - 8

Data Sheet — BAS Remote Specifications (continued) RJ-45 Pin Assignments Modbus (MB) Pin Assignments MDI 10BASE-T/100BASE-TX Terminal Terminal Usage Usage D+ Data + 1 TD + D– Data – 2 TD – SC Signal Common 3 RD + 6 RD – Other pins Not Used Electromagnetic Compatibility Standard Test Method Description Test Levels EN 55024 EN 55024 EN 55024 EN 55024 EN 55024 EN 55024 EN 55022 EN 55022 CFR 47, Part 15 EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6 EN 61000-4-11 CISPR 22 CISPR 22 ANSI C63-4 Electrostatic Discharge Radiated Immunity Fast Transient Burst Voltage Surge Conducted...

Open the catalog to page 8

All Contemporary Control Systems catalogs and technical brochures

  1. DS-PC104220B

    4 Pages

  2. DS-AISRVR00B

    6 Pages

  3. TD9905200D

    3 Pages

  4. TD9905000D

    3 Pages

  5. TD0209000D

    3 Pages

  6. DS-EIS00000B

    4 Pages

  7. DS-EISK8PG0B

    4 Pages

  8. DS-EISK5000B

    4 Pages

  9. DS-EISK5GH0B

    4 Pages

  10. DS-EISK5G00B

    4 Pages

  11. CAN104-DN

    3 Pages

  12. CANISA

    3 Pages

  13. BASgateway

    4 Pages

  14. BASrouter

    8 Pages

  15. BASview

    16 Pages

  16. BAScontrol

    8 Pages

  17. CTRLink®

    6 Pages

Archived catalogs