video corpo

ProFire-S1
4Pages

{{requestButtons}}

Catalog excerpts

ProFire-S1 - 1

Burners with multi-fuel versatility available for Scotch Marine and Watertube applications.

Open the catalog to page 1
ProFire-S1 - 2

Multi-Fuel Versatility. Forced draft duel fuel burner. The Cleaver-Brooks ProFire-S1 series burner forced draft design allows for tried and true trouble-free operation and superior efficiency on scotch marine and watertube boiler applications worldwide. The ProFire-S1 series, available in uncontrolled, and low NOx configurations offers multi-fuel versatility to meet the toughest air quality standards. Precise Oil Metering A unique design feature on ProFire-S1 series air atomizing oil burners, an oil flow control valve is used for maximum capacity and precise oil control. Air Compressor...

Open the catalog to page 2
ProFire-S1 - 3

The S1 Burner Explained: The ProFire-S1 series offers: natural gas, propane gas, air atomized #2-6 oil and combination gas and oil fuel options from 46.2 to 63.0 MM BTU per hour. The LNS1 burner, capable of <30 PPM NOx emissions offers: natural gas, propane gas, air atomized #2 oil and combination gas and oil fuel options from 42.0 to 63.0 MM BTU per hour. Full modulation operation and cam trim are standard for greater efficiency and cost savings. The S1 burner is an excellent choice when firing alternative fuels such as digester, waste oil, and biodiesel. Low-pressure air atomizing system...

Open the catalog to page 3
ProFire-S1 - 4

Uncontrolled Emissions Configuration (S1L, S1G, S1LG) Input is based on fuel Btu content and altitude of 2,000 feet or less. If altitude > 2,000 feet and < 8,000 feet, derate capacity 4% per 1,000 feet over 2,000. Consult factory for higher altitudes. Gas input is based on natural gas with 1,000 Btu/cu.ft. and 0.60 gravity. Oil input based on 150,000 Btu/gal and the aforementioned conditions. Consult factory for 50Hz. applications. Burner Sizes Input is based on fuel Btu content and altitude of 2,000 feet or less. If altitude > 2,000 feet and < 8,000 feet, derate capacity 4% per 1,000 feet...

Open the catalog to page 4

All Cleaver-Brooks catalogs and technical brochures

  1. LCS150e.1

    2 Pages

  2. LCS250e.1

    2 Pages

  3. LevelMaster

    4 Pages

  4. Model 4

    4 Pages

  5. Model 5

    4 Pages

  6. Oil Pump Set

    12 Pages

  7. PCS140e.1

    2 Pages

  8. ProFire-D

    8 Pages

  9. ProFire-NTH

    4 Pages

  10. Stack Damper

    2 Pages

  11. LC ClearFire

    8 Pages

  12. SCR

    4 Pages

  13. FLX Flextube

    8 Pages

  14. ADAC

    2 Pages

  15. 4WI - CBLE

    8 Pages

  16. CBR

    4 Pages

  17. ICB

    8 Pages

  18. CBL

    4 Pages

  19. Ohio Special

    4 Pages