You may also be interested in
Capacitor, Power regulator, Phasemeter, Process indicator, Contactor
Text version of the page
Voltage inputs Digital relay outputs Measurement rangefrom 5 to 120% of U
n for U n = 300 V ac (ph-N)from 5 to 120% of TypeMechanical relay Operation voltage250 V ac Maximum current (resistive load)3 A U n for U n = 520 V ac (ph-ph)Frequency45…65 Hz Maximum measured voltage360 V ac Overvoltage allowance750 V ac (up to) Consumption n for I n = 5 ASecondary CT ( I n )1 or 5 APrimary currentProgrammable 80 to 265 V ac (50 - 60 Hz) (consumption n Operation temperature- 10... + 50 °CStorage temperature- 20... + 65 ºCRelative humidity95% without condensationInstallation categoryCAT III according to IEC 61010Level of contamination2 according to IEC 61010 Protection indexIP51 frontIP20 rear section Voltage (V)± 0,2 % from 20 % ...120 % of U n / U n Active power P± 0,2 % from 10% ... 120 % of I n Reactive power Q± 0,5 % from 10 % ... 120 % of I n Apparent power S± 0,5 % from 10 % ...120 % of I n Frequency F± 0,01 Hz from 45 to 65 HzActive energy± 0,2 %Reactive energy± 0,5 %Apparent energy± 0,5 % MECHANICS ConnectionScrew terminal block for rigid wires of 2.5 mm (4.5 mm 2 ) or exible wires Digital pulse outputs TypeOptocouplerOperation voltage24 dc Maximum power (per output)0.6 W REGULATION REFERENCES CEM 61000-4-2, 61000-4-3, 61000-4-11, 61000-4-4, 61000-4-5 design by: Communication dpt. - CIRCUTOR SA CVMk2, Power analyzer - 11644 Cod.C2M543- 01CIRCUTOR SA, reserves the right to modify the contents of this catalogue |
|