Electric Ventilation Duct Heaters PDS - Chromalox - #1

/ 4


catalogue search
Electric Ventilation Duct Heaters PDS - Chromalox
P. 01
Electric Ventilation Duct Heaters PDS - Chromalox
P. 02
Electric Ventilation Duct Heaters PDS - Chromalox
P. 03
Electric Ventilation Duct Heaters PDS - Chromalox
P. 04
Pages:
Electric Ventilation Duct Heaters PDS - Chromalox


See other catalogues for Chromalox

Text version of the page
NAVY DUCT PDS
VENTILATION DUCT HEATERS
Size 24 EH Type H 5.5 kW
• 0.5 - 183.0 kW
• 1706 - 624,396 BTUH
• 115 or 440 Volts 3 Phase
• Built and Qualified to Military Specification MIL-PRF-22594B (Also Meets MIL-H-22594A)
• Shock Test Qualification per Military Specification
MIL-S-901
• Vibration Test Qualification per Military Specification MIL-STD-167-1
Description
Chromalox Type H, M and L Electric Ventilation Duct Heaters are used in heating, ventilation and air conditioning systems. They are built and qualified to Military Specification MIL-PRF-22594B (also meets MIL-H-22594A).
Features
MONEL® Fintube Heating Elements are provided with nickel chromium resistance wire centered in a densely compacted magne­sium oxide insulation. This is then enclosed in a MONEL® sheath with spiral MONEL® fins continuously wound around the sheath and permanently furnace brazed to the sheath. This construction provides good corrosion resistance, low operating temperatures and long operating life. Heating elements meet Military Specification MIL-H-22577C.
Hermetic Seals are ceramic to metal type, welded on the terminal ends of the heating elements to prevent moisture from entering element internals.
Heater Casing is constructed of 14 and 16-gauge stainless steel. Pre-drilled flanged connections on the inlet and outlet are provided for installation to the duct work.
Electrical Terminal Enclosure is
of a spray-tight construction and fully gasketed to prevent moisture from entering the electrical
connections. The cover plate is removeable for complete acess to the power source terminals.
Manual Reset Cutout thermostat is provided to limit the surface temperature of the heating ele­ments to the 750°F. The cutout switch is located in the electrical terminal enclosure and is resettable from the exterior of the heater.
Electrical Tests on all heaters include:
• Circuit strength test of the electri­cal circuits.
• Insulation resistance check of the heating elements and heater assembly.
• Moisture resistance and dielectric strength tests on each heating element.
• Creepage and clearance checks on electrical components.
• Electrical resistance check and verification of kilowat rating.
First Article Inspection Tests
include:
• Accelerated life tests on heating elements.
• Operational performance test of heating capacity, air flow, pres­sure drop and overtemperature protection.
• Maintainability demonstration.
• Shock test qualification per Military Specification MIL-S-901.
• Vibration test qualification per Military Specification MIL-STD-167-1.
Chromalox"
PRECISION HEAT AND CONTROL
Phone: 1-800-443-2640 • Fax: 412-967-5148 www.chromalox.com ©2006 Chromalox, Inc.

pageCatalog pdf di En 2012-02-07-16