Flowsorb - Calgon Carbon Corporation - #1

/ 4


catalogue search
Flowsorb - Calgon Carbon Corporation
P. 01
Flowsorb - Calgon Carbon Corporation
P. 02
Flowsorb - Calgon Carbon Corporation
P. 03
Flowsorb - Calgon Carbon Corporation
P. 04
Pages:
Flowsorb - Calgon Carbon Corporation


See other catalogues for Calgon Carbon Corporation

Text version of the page
Untitled
Description
Designed for low-flow water treatment applications, prefabricated 55-gallon FLOWSORB® canisters contain all the operating elements found in a full-scale adsorption system. These small, economical treatment systems hold 180 pounds of granular activated carbon for applications including:
• Small wastewater streams
• Groundwater remediation
• Underground storage tank leaks
• Well pump tests
• Product purification or de-colorization
• Tank cleaning water treatment
• Batch water or product treatment
• Carbon adsorption pilot testing
• Emergency spill treatment
• Monitoring well water treatment
Spécifications
Vessel Open head steel canister
Cover Removable steel cover, 12 gauge
bolt ring
Internal Coating Heat-cured phenolic epoxy
External Coating Baked enamel (white)
Temperature Limit 150°F (65.6°C) continuous
250°F (l21.1°C) intermittent
Inlet 2" FNPT
Outlet 2" FNPT
Carbon 180 lbs. granular activated
carbon: Specify FILTRASORB® 300 or reactivated grade
Ship Weight 219 lbs. (99.4 kg)
Identification Sequentially numbered for
traceability
Features
FLOWSORB® offers several features and benefits to industrial, commercial, and municipal users including:
• Low cost per unit makes carbon treatment economical
• Simple installation and operation
• Space above carbon bed facilitates flow distribution or back-flushing
• Flexibility to be used in series or parallel operation
• Supplied with virgin or reactivated carbon
• Practical disposal option: pre-approved spent carbon canisters may be returned to Calgon Carbon Corporation for safe carbon reactivation
• Continuous treatment at various flow rates and concentrations
Pressure Drop
Typical Operating Parameters
Flow Rate
10 gpm (37.8 l/m)
Contact Time
4.5 minutes
Pressure Drop
< 1 psi (clean water and carbon)
Operating Pressures
Recommend operation at less
than 5 psig
<
CAI
CAL
ON CORP
DRATION
0 2 4 6 8 10 12
Gallons Per Minute
Making Water and Air Safer and Cleaner

pageCatalog pdf di En 2012-05-22-28