BRODERSEN
Compact utility outstation / EN/IEC60870-5-101 slave
RTU870
CONFIGURATION
The RTU870 Configuration program is used to configure the RTU870. The configuration tool makes it possible to setup both hardware specific and protocol specific parameters. Refer to the RTU870 Configuration tool user guide for more info.
For experienced user, the IO Explorer can also be used. With this tool you may configure the RTU870 with additional control features, change many protocol specific parameters. High level programming skills required.
RTU870 Configuration fields
A number of configuration fields are provided. The field values are changed and downloaded into the RTU flash memory, using the RTU870 Configuration menu. The fields are used for values that are programmed once when setting up the module (e.g. baud rate). The following fields are provided to control the RTU with the actual interfaces including the EN/IEC60870-5-101 slave port driver.
RTU870configuration table
RTS Trailing
Defines the delay from the RTU is transmitting the last character to de­activating RTS.
Retry count
Defines the number of retries which should be made to the same telephone number before giving up or continuing to the next number, if the call is not successful. Default value: 3, Range: 0 .. 10.
Max comm cnt.
Defines the number of times the input and output will be read and written before the module makes a hang-up. If Max Com Count=256 the PC is responsible for correct hang-up. This option should normally not be changed.
Subs. to try.
Defines the number of subscribers to try after being through the number of retries on the first number in the list of phone numbers. If the value is set to 3, it will try number 1, 2 and 3 in the phone no list. Default value: 1, Range 1-10.
Redial delay.
Defines the delay from an unsuccessful attempt to dial to a new attempt to establish connection. Default value: 90 sec, Range: 2-120 sec.
Tel. no.
The maximum number of telephone numbers stored in RTU is 30, the maximum length is 20 characters. The telephone numbers can although include some special characters to control the dialling function of the modem.
Modem init.
The modem initialisation string has a maximum length of 60 charac­ters. This string contains the configuration data for the connected modem. It will be sent cyclic to the modem and every time a connection is established by the RTU. Default value: ATV0E0&C1S0
PIN code.
If GSM modem is used and PIN code is required for the SIM card, the PIN code must be entered here. Be careful to enter the right PIN code - if not, the three normal attempts will quickly be used up and a PUK code is required to re-open the SIM card again. Use a normal mobile telephone to change PIN code parameters and enter PUK codes.
Default: blank
Modem Reinit.
Defined the time in minutes between cyclic re-initialisation of the modem. If the modem of some reason is reset and the required modem settings not has been save in the modem flash, the modem will start up with its default settings. With this option you can make sure that the modem is initialised periodically. Default value: 0 min, range 0-999min.
Dial back
Enable or disable the dial back function.
User
User defined value. Constant value can be used in B-CON application / IEC870
Date/Time
Real time clock adjustment. The actual time in the module can be monitored and adjusted either by entering the time or by copying the PC clock to the module.
Property Value Unit
Baud rate 9600 IEC870-5-101
Use E5 resp. Ack/No data IEC870-5-101
Resp. Delay 1 of 10 msec
RTS Leading 5 of 10 msec
RTS Trailing 1 of 10 msec
Retry count 3
Max comm cnt 256
Subs to try 1
Redial delay 90 Seconds
Tel. no. (Table)
Modem init. (Table)
PIN Code (Table)
Modem Reinit 37 Minutes
Dial back Disabled
User 0
Date/Time (Clock)
Boot delay 2 Seconds
S0 Cnt Type Accumu.
S0 Interval 3 Minutes
Analog Range 0...20 mA
Port A cfg.
This is the header for the configuration of IEC870-5-101 parameters Baud rate
Define the baud rate for the main serial port. 300-9600 baud. This option is not available in the RTU560S with built-in V23 modem.
Use E5 resp
Option for using E5 response. It is possible to select; Not used, used as acknowledge and used as acknowledge and no data.
Resp. Delay
Defines the response delay in times of 10ms. RTS Leading
Defines the delay from the RTU is activating the RTS to the transmission of the first character.
Brodersen Controls A/S * Industrivej 3 * DK-4000 Roskilde
Denmark * Tel (+45) 4674 0000 * Fax (+45) 4675 7336
16
40154/48.05
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18
page 19 p.19
page 20 p.20
page 21 p.21
page 22 p.22
page 23 p.23
page 24 p.24
page 25 p.25
page 26 p.26
page 27 p.27
page 28 p.28
page 29 p.29
page 30 p.30
page 31 p.31
page 32 p.32
page 33 p.33
page 34 p.34
page 35 p.35
page 36 p.36
page 37 p.37
page 38 p.38
page 39 p.39
pdf-page pdf di En 2008-12-49-01