Residual current monitor RCM465Y Wiring diagram – system connection, external connections Wiring diagram – front plate
4.1

Residual Current Monitors - 14922 1 2 12345

1 - TEST button2 - Power On LED3 - Alarm LED: lights when the fault current exceeds the response value.4 - Potentiometer for setting the response delay (0…1 s).5 - Potentiometer for setting the response value (30…300 mA). 1 - Supply voltage U
S (see ordering details), a 6 A fuse is recom-mended.2 - Alarm relay: switches when the response value is reached. Note! Do not route the PE conductor through the measuring current transformer!
Main catalogue part 4 – 04.2007/Residual current monitors, Residual current monitoring systems 51

pageCatalog pdf di En 2012-05-22-28