video corpo

ISOMETER® isoLR275 with AGH-LR
6Pages

{{requestButtons}}

Catalog excerpts

ISOMETER® isoLR275 with AGH-LR - 1

The Power in Electrical Safety® ISOMETER® isoLR275 with coupling device AGH-LR Insulation monitoring device for unearthed IT AC, AC/DC and DC systems for electrical installations with a low level of resistance

Open the catalog to page 1
ISOMETER® isoLR275 with AGH-LR - 2

Insulation monitoring device for unearthed IT AC, AC/DC and DC systems for electrical installations with a low level of resistance with coupling device AGH-LR Product description The isoLR275 ISOMETER® in conjunction with the AGH-LR coupling device monitors the insulation resistance of IT systems. It is suitable for universal use in 3(N) AC, AC/DC and DC systems. AC systems may include extensive DC-supplied loads, such as converters or thyristor-controlled DC drives. The adaptation to the existing system leakage capacitances takes place automatically. Only use the AGH-LR coupling device...

Open the catalog to page 2
ISOMETER® isoLR275 with AGH-LR - 3

ISOMETER® isoLR275 with coupling device AGH-LR Wiring diagram 1 - INFO” button: to query standard information/ “ “ESC” button: back (menu function), to confirm parameter change 2 - TEST” button: to call up the self test/arrow up button: “ parameter change, to move up in the menu 3 - RESET” button: to delete stored insulation fault alarms “ Arrow down button: parameter change, to move down in the menu 4 - MENU” button: to call up the menu system. “ Enter button: to confirm parameter changes 5 - larm LED “1” lights: insulation fault, first warning level reached A 6 - larm LED “2” lights:...

Open the catalog to page 3
ISOMETER® isoLR275 with AGH-LR - 4

ISOMETER® isoLR275 with coupling device AGH-LR Z BENDER Insulation coordination acc. to IEC 60664-1/IEC 60664-3 Rated insulation voltage for isoLR275-3 AC 250 V Rated impulse voltage/pollution degree 6 kV/III Voltage test acc. to IEC 61010-1 Rated insulation voltage Rated impulse voltage/pollution degree Basic insulation between: Voltage test acc. to IEC 61010-1 Serial interface Interface/protocol Connection Cable length Shielded cable (shield to pe on one end) Terminating resistor Device address, BMS bus Voltage ranges Nominal system voltage Un isoLR275-335: Supply voltage Us (also...

Open the catalog to page 4
ISOMETER® isoLR275 with AGH-LR - 5

ISOMETER® isoLR275 with coupling device AGH-LR Technical data coupling device AGH-LR Dimension diagram XM112 – ISOMETER® isoLR275 Dimensions in mm Insulation coordination acc. to IEC 60664-1 Rated insulation voltage Rated impulse voltage/pollution degree Nominal system voltage Un AC, 3(N)AC 0…793 V, DC 0…1100 V Nominal frequency fn DC, 10…460 Hz Max. AC voltage U~ in the frequency range fn = 0.1…10 Hz U~max = 110 V/Hz * fn Environment/EMC EMC IEC 61326-2-4 Ed. 1.0 Operating temperature -25…+70 °C Classification of climatic conditions acc. to IEC 60721: Stationary use (IEC 60721-3-3) 3K5...

Open the catalog to page 5
ISOMETER® isoLR275 with AGH-LR - 6

BENDER Group isoLR275_D00127_00_D_XXEN / 06.2015 / pdf / © Bender GmbH & Co. KG, Germany – Subject to change! The specified standards take into account the version that was valid at the time of printing. Bender GmbH & Co. KG P.O. Box 1161 • 35301 Gruenberg • Germany Londorfer Strasse 65 • 35305 Gruenberg • Germany Tel.: +49 6401 807-0 • Fax: +49 6401 807-259 E-Mail: info@bender.de • w

Open the catalog to page 6

All BENDER catalogs and technical brochures

  1. CTBC17

    2 Pages

  2. POWERSCOUT®

    8 Pages

  3. Energy meter

    6 Pages

  4. RDC121

    7 Pages

  5. RCMB123

    7 Pages

  6. RCMB 121-2

    7 Pages

  7. RCMB121-1

    7 Pages

  8. RDC104-4

    6 Pages

  9. 300ST

    4 Pages

  10. 400ST

    4 Pages

  11. USC710D4

    6 Pages

  12. DI-1DL

    4 Pages

  13. DI-2

    4 Pages