Portable insulation fault location systemsEDS3065/EDS3365

Function insulation fault evaluator Once the installed PGH185/183 insulation fault test device has been activated, the measuring clamps of the portable EDS165/-3 evaluator are placed around all conductors of the individual circuits (with the exception of PE). When the measuring value in a faulty subcircuit exceeds the response value, the alarm LED lights up and an audible signal sounds. The value of the test current is indicated on the display. The alarm message can be stored. Not only can current clamps be used to detect the measuring values, but also permanently installed or split-core measuring current transformers. An additional function allows measuring residual currents in earthed systems (TN/TT systems) too. The operating mode can be changed via a selector switch. Residual currents in the range of 10 mA…1 A (EDS165-3) resp. 10 mA…10 A (EDS165) can be measured. Displays The LC display indicates the measured value of the test current, the type of the connected measuring current transformers resp. current clamps, the accumulator capacity, the activation of the alarm memory, the activation of the buzzer, and the set nominal frequency. •
Portable insulation fault location systems EDS3065/EDS3365 Device features Insulation fault location sy-stem for IT systems EDS3065 • Accumulator charging set included in the scope of delivery• RS-232 interface • Current clamps 20/52 mm• Current clamp 100 mmoptional for EDS3065• Residual current measure-ment in TN/TT systems EDS3065: 10 mA…10 A EDS3365: 10 mA…1 A• Portable insulation fault test device AC 20…575 V/DC 20…504 V – EDS3365 AC 20…265 V/DC 20…308 V• Response values: EDS3065 5 mA, EDS3365 0.5 mA• LC display • Alarm LED• Switchable operating mode: insulation fault location/re-sidual current measurement • Technical data EDS3360/3365 Insulation coordination acc. to IEC 60664-1 Rated insulation voltage EDS3065 AC 500 V, EDS3365 AC 250 VRated impulse voltage/pollution degree 4 kV/3 Voltage ranges Nominal system voltage U
n see ordering informationSupply voltage U Supplied by an accumulator
S see ordering informationOperating range of U
s 0.85…1.15 x U
s Approval Power consumption ≤ 3 VA Storage battery charger AC 100…240 V Test current Selectable, max. value EDS 3065 10/25 mA; EDS3365 1/2.5 mA Response values Product description Test current response value EDS 3065 5 mA; EDS3365 0.5 mA The EDS3065/3365 is a portable system designed to locate insula-tion faults in unearthed systems (IT systems). The EDS3065 is desi-gned to be used in AC 20…575 V/DC 20…504 V systems, the EDS3365 is designed to be used in AC 20…265 V/DC 20…308 V. The robust aluminium case incorporates an EDS165/165-3 insula- tion fault evaluator, a PGH18... insulation fault test device, diffe-rent types of current clamps as well as various accessories. Outputs Interface RS-232 Displays LC display LC 2 x 16 charactersLED Alarm
1.7 Application General data • EDS3065 system for insulation fault location in main circuits• EDS3365 system for insulation fault location in control circuits• For occasional location of insulation faults in small or medium-sized IT systems Shock resistance IEC 60068-2-27
(during operation) 15 g/11 msBumping IEC 60068-2-29
(during transport) 40 g/6 msVibration resistance IEC 60068-2-6
(during operation) 1 g/10…150 HzVibration resistance IEC 60068-2-6 Function insulation fault test device
(during transport) 2 g/10…150 HzAmbient temperature The PGH18… insulation fault test device should be connected preferably at the power supply infeed of the system being moni-tored. Once being switched on, the PGH18... generated a defined test current signal. The existing system voltage is used to drive the test current. The test current generated in this manner de-pends on the size of the present insulation fault and the system voltage. The test current is limited to 25/2.5 mA resp. 10/1 mA, depending on the switch position and device type. The cycle of the test current is indicated via alarm LEDs.
(during operation) - 10 °C…+ 55 °CAmbient temperature
(during storage) - 40 °C…+ 70 °CClimatic class acc. to DIN IEC 60721-3-3 3K5Operating mode continuous operationMounting any position Degree of protection acc. to DIN EN 60529 IP 20 Flammability class UL94V-0Product standards DIN EN 61557-9: 2000-08 EN 61557-9: 1999-11, IEC 61557-9: 1999-09 Operating value EDS3065 TGH 1266; EDS3365 TGH1320Weight ≤ 7000 g (≤ 8500 g with PSA3165)
Main catalogue part 1 – 08.2007/Insulation monitoring 101