BEBENDER
A-ISOMETER® IR42C
Technical data A-ISOMETER® IR420
Switching elements
Number of switching elements
2 x 1 changeover contact
Operating principle
N/C or N/O operation (N/O operation)*
Electrical service life
10.000 switching operations
Contact data acc. to IEC 60947-5-1
Utilization category
AC-13 AC-14 DC-12 DC-12 DC-12
Rated operational voltage
230 V 230 V 220 V 110 V 24 V
Rated operational current
5 A 3 A 0.1 A 0.2 A 1 A
Minimum current
1 mA at AC/DC > 10 V
Environment/EMC
EMC
IEC 61326
Operating temperature
- 25 "C...+ 55 °C
Climatic class acc. to IEC 60721
Stationary use (IEC 60721-3-3)
3K5 (except condensation and formation of ice)
Transport (IEC 60721-3-2)
2K3 (except condensation and formation of ice)
Long-time storage (IEC 60721-3-1)
1K4 (except condensation and formation of ice)
Classification of mechanical conditions IEC 60721
Stationary use (IEC 60721-3-3)
3M4
Transport (IEC 60721-3-2)
2M2
Long-time storage (IEC 60721-3-1)
1M3
Connection
Connection
screw-type terminals
rigid/flexible/conductor sizes
0.2...4/0.2...2.5 mm2/24-12 AWG
Multi-conductor connection (2 conductors with the same cross section)
rigid/flexible
0.2...1.5/0.2...1.5 mm2
Stripping length
8...9 mm
Tightening torque
0.5...0.6 Nm
Other
Operating mode
continuous operation
Mounting
any position
Degree of protection, internal components (IEC 60529) IP30
Degree of protection, terminals (IEC 60529) IP20
Enclosure material
polycarbonate
DIN rail mounting acc. to
IEC60715
Screw mounting
2 x M4 with mounting clip
Product standards
DIN EN 61557-8:1998-05,EN 61557-8: 1997-03,
IEC 61557-8: 1997-02, ASTM F 1207M-96 (2002)
Operating manual
BP101012
Weight
< 150 g
Insulation coordination acc. to IEC 60664-1/IEC 60664-3
Rated insulation voltage
250 V
Rated impulse voltage/pollution degree
2.5 kV / III
Protective separation (reinforced insulation) between
(A1, A2) - (L1, L2, E, KE, T/R) - (11, 12, 14) - (21, 22, 24)
Voltage test according to IEC 61010-1
2.21 kV
Supply voltage
Supply voltage Us
see ordering information
Power consumption
< 3 VA
IT system being monitored
Nominal system voltage Un
AC 0...300V
Rated frequency fn
42...460 Hz
Response values
Response value Ran1 (Alarm 1)
1...200 kQ
Response value Ran2 (Alarm 2)
1...200 kQ
Preset mode Un < 72 V Ran1 (Alarm 1) =
20 kQ/Ran2 (Alarm 2) = 10 kQ
Un > 72 V Ran1 (Alarm 1) =
46 kQ/Ran2 (Alarm 2) = 23 kQ
Operating error 1 kQ. „5 kQ/5 kQ. „200 kQ
± 0.5 kQ/± 15%
Hysteresis
25%
Specified time
Response time tan at Rf = 0.5 x Ran and Ce = 1 uF
< 1 s
Start-up delay t
0...10 s (0 s)*
Response delay ton
0...99 s (0 s)*
Measuring circuit
Measuring voltage Um
12 V
Measuring current Im (at Rf = 0 Q)
< 200 uA
Internal DC resistance Ri
> 62 kQ
Impedance Zi at 50 Hz
> 60 kQ
Permissible extraneous DC voltage Ufg
< DC 300 V
Permissible system leakage capacitance Ce
< 20 uF
Displays, memory
Display range, measuring value
1 kQ„.1 MQ
Operating error 1 kQ„.5 kQ/5 kQ„.1 MQ
± 0.5 kQ/± 15%
Password
off / 0...999 (off)*
Fault memory, alarm relay
on/off*
Outputs
Cable length test and reset button
< 10 m
factory setting
Ordering information
Typ
Nominal system voltage* Un
Supply voltage* Us
Response value Ran
System leakage capacitance Ce
Art. No.
IR420-D4-1
AC 42...460 Hz 0...300 V
DC 9,6„.94 V/AC 42...460 Hz 16...72 V
1...200 kQ
< 20 uF
B91016409
IR420-D4-2
AC 42...460 Hz 0...300 V
DC 70.. .300 V/AC 42.. .460 Hz 70.. .300 V
1...200 kQ
< 20 uF
B91016405
absolute values
Accessories
Type
Art. No.
Mounting clip for screw mounting
B 9806 0008
(one piece per device)
Main catalogue part 1 - 08.2007/Insulation monitoring
34
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18
page 19 p.19
page 20 p.20
page 21 p.21
page 22 p.22
page 23 p.23
page 24 p.24
page 25 p.25
page 26 p.26
page 27 p.27
page 28 p.28
page 29 p.29
page 30 p.30
page 31 p.31
page 32 p.32
page 33 p.33
page 34 p.34
page 35 p.35
page 36 p.36
page 37 p.37
page 38 p.38
page 39 p.39
page 40 p.40
page 41 p.41
page 42 p.42
page 43 p.43
page 44 p.44
page 45 p.45
page 46 p.46
page 47 p.47
page 48 p.48
page 49 p.49
page 50 p.50
Pages:
1-50
51-100
101-150
151-200
201-212
pdf-page pdf di En 2008-11-47-23