| | Switching elements | | |
| | Number of switching elements | 2 x 1 changeover contact | |
| | Operating principle | N/C or N/O operation (N/O operation)* | |
| | Electrical service life | 10.000 switching operations | |
| | Contact data acc. to IEC 60947-5-1 | | |
| | Utilization category | AC-13 AC-14 DC-12 DC-12 DC-12 | |
| | Rated operational voltage | 230 V 230 V 220 V 110 V 24 V | |
| | Rated operational current | 5 A 3 A 0.1 A 0.2 A 1 A | |
| | Minimum current | 1 mA at AC/DC > 10 V | |
| | Environment/EMC | |
| | EMC | IEC 61326 | |
| | Operating temperature | - 25 "C...+ 55 °C | |
| | Climatic class acc. to IEC 60721 | | |
| | Stationary use (IEC 60721-3-3) | 3K5 (except condensation and formation of ice) | |
| | Transport (IEC 60721-3-2) | 2K3 (except condensation and formation of ice) | |
| | Long-time storage (IEC 60721-3-1) | 1K4 (except condensation and formation of ice) | |
| | Classification of mechanical conditions IEC 60721 | |
| | Stationary use (IEC 60721-3-3) | 3M4 | |
| | Transport (IEC 60721-3-2) | 2M2 | |
| | Long-time storage (IEC 60721-3-1) | 1M3 | |
| | Connection | |
| | Connection | screw-type terminals | |
| | rigid/flexible/conductor sizes | 0.2...4/0.2...2.5 mm2/24-12 AWG | |
| | Multi-conductor connection (2 conductors with the same cross section) | |
| | rigid/flexible | 0.2...1.5/0.2...1.5 mm2 | |
| | Stripping length | 8...9 mm | |
| | Tightening torque | 0.5...0.6 Nm | |
| | Other | |
| | Operating mode | continuous operation | |
| | Mounting | any position | |
| | Degree of protection, internal components (IEC 60529) IP30 | |
| | Degree of protection, terminals (IEC 60529) IP20 | |
| | Enclosure material | polycarbonate | |
| | DIN rail mounting acc. to | IEC60715 | |
| | Screw mounting | 2 x M4 with mounting clip | |
| | Product standards | DIN EN 61557-8:1998-05,EN 61557-8: 1997-03, | |
| | | IEC 61557-8: 1997-02, ASTM F 1207M-96 (2002) | |
| | Operating manual | BP101012 | |
| | Weight | < 150 g | |
| | | | |