Undervoltage and overvoltage relay SUA200Z Wiring diagram Bestellangaben Type Nominal system voltage U
n Response delay Art. No. SUA200Z AC/DC 24 V 0.5…5 s B 932 361 SUA200Z AC/DC 42 V 0.5…5 s B 932 316SUA200Z AC/DC 48 V 0.5…5 s B 932 313SUA200Z AC/DC 60 V 0.5…5 s B 932 255 SUA200Z AC/DC 100 V 0.5…5 s B 932 223SUA200Z AC/DC 110 V 0.5…5 s B 932 220SUA200Z AC/DC 220 V 0.5…5 s B 932 172 SUA200Z AC/DC 230 V 0.5…5 s B 932 634SUA200Z AC/DC 24 V 2…20 s B 932 362SUA200Z AC/DC 42 V 2…20 s B 932 317 SUA200Z AC/DC 48 V 2…20 s B 932 314 SUA200Z AC/DC 60 V 2…20 s B 932 256 SUA200Z AC/DC 100 V 2…20 s B 932 224 SUA200Z AC/DC 110 V 2…20 s B 932 221 SUA200Z AC/DC 220 V 2…20 s B 932 173

Electronic measuring and monitoring relays - 14922 123456798

3.1 Dimension diagram X200 Dimensions in mm 1 - 6 A fuse2 - Alarm LED undervoltage “n ”3 - Power On LED “on”4 - Alarm LED overvoltage “>U
n ”5 - Setting potentiometer for time delay “t/s”6 - Setting potentiometer for undervoltage “xU
n ”7 - Setting potentiometer for overvoltage “xU
n ”8 - Alarm relay for signalling undervoltage and overvoltage9 - AC system: Bridge terminal 1 with terminal 2 DC system: Terminal 1 and 2 remain unassigned. Technical data undervoltage and overvoltage relay SUA200Z Insulation coordination acc. to IEC 60664-1 Environment / EMC Rated insulation voltage AC 250 VRated impulse voltage/pollution degree 2.5 kV/3 EMC immunity acc. to IEC 61000-6-2EMC emission acc. to IEC 61000-6-4Shock resistance IEC 60068-2-27 (during operation) 15 g/11 ms Bumping IEC 60068-2-29 (during transport) 40 g/6 ms Vibration resistance IEC 60068-2-6 (during operation) 1 g / 10…150 Hz Vibration resistance IEC 60068-2-6 (during transport) 2 g / 10…150 Hz Ambient temperature, during operation -15…+60 ΊC Ambient temperature during storage -20…+70 ΊC Climatic class acc. to IEC 60721-3-3 3K5 Other Operating mode continuous operationMounting any position Connection Flat terminals with self-lifting clamp washersConnection propertiessingle wire 2 x (1…1.5) mm Supply voltage Supply voltage U
S nonePower consumption ≀ 3 VA Measuring circuit Nominal system voltage U
n see ordering information Rated frequency f
n DC, 40…400 HzResponse values (undervoltage) 0.7…0.95 x U
n Response values (overvoltage) 1.05…1.3 x U
n Response delay t
v 2…20 s / 0.5…5 sHysteresis approx. 3 % Recovery time t Switching elements
b 5 sDelay on release approx. 400 ms Repitition accuracy 1.4 % Temperature influence
2 flexible with end ferrules 2 x (0.75…1.5) mm
2 Degree of protection, internal components (IEC 60529) IP50 Degree of protection, terminals/with terminal covers (IEC 60529) IP10/IP20 Screw fixing refer to dimension diagram DIN rail mounting acc. to IEC 60715 Flammability class UL94V-0Product standard IEC 60255-6Operating manual BP301003 Weight ≀ 300 g
Main catalogue part 3 – 06.2007 / Electronic measuring and monitoring relays 39

pageCatalog pdf di En 2012-05-22-28