Specifications are subject to changes without notice. 11 / 05 KTM-US 923-0876 01/1
Technical Data
Mechanical Temperature Switches
P5
Features
- Single switch T1X, T1X-Ex and
dual switch T2X, T2X-Ex with remote sensor
- Weatherproof housing
- Covered terminal strip and set point adjustment
- Protection class NEMA 4 / 7 / 9
- Optional:
- T2X: Manual reset, G-microswitch with one contact,
- T1X: Adjustable hysteresis (reset difference),
S-microswitch with one contact
- Special version for track heating systems
with ratings up to 32 A / 220 V
Measuring Ranges
-45 °C...+66 °C to +160 °C...+316 °C
Applications
Temperature monitoring and control
in chemical industry and oil industry, offshore
Housing material : Die-cast aluminum
Temperature sensor material : Stainless steel (316SS)
Temperature sensor : Capillary length 1,8 m or 3,6 m (optional 7,5 m), armoured
Sensor without thermowell is applicable up to 21 bar only
Electrical characteristics : All models are SPDT
Microswitch : H, M, GH, GM, S with adjustable hysteresis
Contact rating : - AC: 125 V AC to 250 V AC, 10 A
480 V AC, 3 A
- DC: 6 V DC to 24 V DC, 0,5 A
Electrical connection : From the terminal strip through a 1/2“ NPT conduit connection (T1X / T1X-Ex) resp.
3/4“ NPT conduit connection (T2X / T2X-Ex) outside.
Protection class : NEMA 4 / 7 / 9 (T1X and T2X), intrinsically safe acc. EEx ia II C for gases and dust
Ex-Protection class : EEx-d (flameproof)
Set point adjustment : Turn adjustment knob clockwise to increase actuation point
Standards : The instruments fullfill the requirements of following harmonized european standards:
EN 60014 1977 + A1 to A4 and EN 500120 1977 + A1
Electrical characteristics : Umax = 28 V DC or 20 Veff, Imax = 50 mA DC or 35 mAeff
Exi-model To comply with the intrinsically safe approval, IS curcuits with the
following maximum ratings have to be used:
Umax = 28 V and Imax = 50 mA
Approvals : Various approvals on request
Weight : appr. 2 kg
with capillary
T1X / T1X-Ex / T2X / T2X-Ex
|
|