Mechanical Temperature Switches - Barksdale - #14 |
|
You may also be interested in
Sensor, Float level switch, Magnetic level indicator, Magnetic level switch, Hydrostatic level sensor
Text version of the page
Specifications are subject to changes without notice. 11 / 05 KTM-US 923-0876 01/1
P11
Local mount type
Technical Data
Mechanical Temperature Switches
Features
- Dual switch with remote sensor and weatherproof housing
- integrated terminal strip and covered set point adjustment
- Protection class IP65
- For use as two-position controller optional with one microswitch
for temperature control with adjustable hysteresis
- The second contact can also be used for max.- or min.-
monitoring or for sensor monitoring
- Optional for 1st contact:
- Manual reset G-microswitch
- Adjustable hysteresis (reset difference) S-microswitch
- Option Thermowell: W = brass ,
WS = CrNi-steel SS316Ti, 1.4571
Measuring Ranges
-54...+24 °C to +149...+232 °C
Applications
Temperature monitoring in industry, shipbuilding, railcars
Housing material : Die-cast aluminum
Process connection : Standard 1/2“ NPT, Option W/WS 3/4“ NPT
Temperature sensor rmaterial : Standard: brass / copper, model S: CrNi-steel (304SS, 1.4301),
pressure values see table on page 16 „Accessories“
Electrical characteristics : All models are SPDT
Microswitch : H, M, GH, GM (optional with RD manual reset for the 1st switching contact only)
Contact rating : - AC: 125 V AC to 250 V AC, 10 A
480 V AC, 3 A
- DC: 6 V DC to 24 V DC, 0,5 A
Electrical connection : 3/4“ NPT female, internal screw terminal, cable gland in PA,
range 6...12 mm is provided
Protection class : IP65, intrinsically safe acc. EEx ia II C for gases and dust
Set point adjustment : Turn adjustment knob clockwise to increase actuation point
Standards : The instruments fullfill the requirements of following harmonized european standards:
EN 60014 1977 + A1 to A4 and EN 500120 1977 + A1
Electrical characteristics : Umax = 28 V DC or 20 Veff, Imax = 50 mA DC or 35 mAeff
Exi-model To comply with the intrinsically safe approval, IS curcuits with the
following maximum ratings have to be used:
Umax = 28 V and Imax = 50 mA
Approvals : Various approvals on request
Weight : appr. 1,5 kg
L2H
|
|