SAFETY MODULES
Muting Modules
MMD-TA-12B & MMD-TA-11B Muting Modules Specifications
Supply Voltage and Current
+24V dc ±15% @ 400 mA max (not including draw of the MSSI power, AUX, ML, M1-M4 and OSSD connections)
Supply Protection Circuitry
All inputs and outputs are protected from short circuit to +24V dc or dc common.
Output Response Time
Muteable Safety Stop Interfaces (MSSI) and the Safety Stop Interfaces (SSI) are less than or equal to 10 milliseconds (MMD-TA-12B) or 30 milliseconds (MMD-TA-11B).
Safety Outputs
MMD-TA-12B:
Two diverse-redundant solid-state safety outputs: 24V dc, 0.5A sourcing OSSD (output signal switching device). ON-State voltage: >V in-1.5V dc
Max. leakage current: 1.2 mA; inclusive of faults (including open 0V dc wire) OFF-State voltage: 1.2V dc max. Max. load capacitance: 0.1 uF
Non-safety auxiliary output: PNP solid-state output, rated at +24V dc @ 250 mA. OSSD test pulse width: 50 to 100 microseconds OSSD test pulse period: 12 milliseconds
MMD-TA-11B:
Output(K1 & K2): Two normally open OSSD (output signal switching device) output channels and one normally closed auxiliary output channel. Each normally open OSSD output channel is a series connection of contacts from two forced-guided (positive-guided) relays—AgNi, 5 um gold-plated
to
LLI _l
Q O S
>-I-
LLI LL.
<
to
Low Current Rating:
Min. voltage: 1V ac/dc Min. current: 5 mA ac/dc Min. power: 5 mW (5 mVA)
High Current Rating: Min. voltage: 15V ac/dc
Min. current: 30 mA ac/dc Min. power: 5 W (5 VA)
Max. voltage: 60V ac/dc Max. current: 300 mA ac/dc Max. power: 7 W (7 VA)
PICO-GUARD CONTROLLERS
E-STOP/GUARD MONITORING
Max. voltage: 250V ac/dc
Max. current: 6 A ac/dc
Max. power: 200 W (1500 VA)
SAFETY MAT
MONITORING
Mechanical life: 50,000,000 operations
Electrical life: 100,000 operations (typical at 200 W/1500 VA, resistive load)
MUTING
MODULES
EXTENSION
MODULES
+24V dc ±15% @ 2.5A max. output (dependent on System power input). Resettable 2.5A industrial fuse
Status Indicators
3 Status Indicator LEDs (Red, Green and Yellow): indicate Power ON/OFF, operating mode, lockout, override, and OSSD status
Green LEDs adjacent to individual inputs/interfaces indicate status (ON = active/closed)
INTERFACE MODULES
Diagnostic Code Display
Diagnostic Display is a two-digit numeric display that indicates the cause of lockout conditions and the amount of time, in seconds, remaining for the backdoor timer.
Muting Lamp Output
A non-monitored sinking output. Max. switching voltage: 30V dc Max. switching current: 360 mA
Min. switching current: 10 mA
Saturation voltage: < 1.5V dc @ 360 mA
Controls and Adjustments
All configured on two redundant banks of Dip switches:
Manual/auto reset
One-way/two-way muting One-channel/two-channel/no EDM
Backdoor timer
Mute on power-up enable
128 More information online at bannerengineeringxgijnri
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
Contents table
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18
page 19 p.19
page 20 p.20
page 21 p.21
page 22 p.22
page 23 p.23
page 24 p.24
page 25 p.25
page 26 p.26
page 27 p.27
page 28 p.28
page 29 p.29
page 30 p.30