Outputs (K1 & K2): four redundant (total of eight) safety relay (forced-guided) contacts - AgNi, 5 urn gold-plated, plus 1 normally closed auxiliary monitor output - AgNi, 5 um gold-plated. Low Current Rating: Caution: The 5 um gold-plated contacts allow the switching of low current/low voltage. To preserve the gold plating on the contacts, the following max. values should not be exceeded at any time: Min. voltage: 1V ac/dc Max. voltage: 60V Min. current: 5 mA ac/dc Max. current: 300 mA Min. power: 5 mW (5 mVA) Max. power: 7 W (7 VA) High Current Rating: If higher loads must be switched through one or more of the contacts, the minimum and maximum values of the contact(s) changes to: Min. voltage: 15V ac/dc Max. voltage: 250V ac/dc Min. current: 30 mA ac/dc Max. current: 6 A Min. power: 5 W (5 VA) Max. power: 200 W (1,500 VA) Mechanical life: 50,000,000 operations Electrical life: 150,000 operations (typical, @ 1,500 VA switched power, resistive load) 150,000 operations (typical, @ 200 W switched power, resistive load) Note: Transient suppression is recommended when switching inductive loads. Install suppressors across load. Never install suppressors across output contacts. Solid-State Monitor Outputs: - Two non-safety solid-state dc outputs - Output at Y32 monitors state of outputs - conducts (output high) when both K1 and K2 are energized - Output at Y35 conducts (output high) when internal power supply is OK - Output circuits require application of 24V dc ±15% at terminal Y31; dc common at Y30 - Maximum switching current: 100 mA at 24V dc - Both outputs are protected against short circuits |