SAFETY MODULES
E-Stop and Guard Monitoring Modules
ES-FA-..AA Safety Module Specifications
Supply Voltage and Current
24V ac/dc, +/- 10%; 50/60Hz
Power consumption: approx. 2 W/2 VA
Supply Protection Circuitry
Protected against transient voltages and reverse polarity
Output Configuration
ES-FA-9AA: 3 normally open output channels
ES-FA-11AA: 2 normally open output channels and 1 normally closed auxiliary output channel.
Each normally open output channel is a series connection of contacts from two forced-guided (positive-guided) relays, K1-K2.
The normally closed contact 31-32 is a parallel connection of contacts from K1-K2.
Contacts: AgNi, 5 urn gold-plated Low Current Rating:
Caution: The 5 pm gold-plated contacts allow the switching of low current/low voltage.
To preserve the gold plating on the contacts, the following max. values should not be exceeded at any time: Min. voltage: 1V ac/dc Max. voltage: 60V
Min. current: 5 mA ac/dc Max. current: 300 mA
Min. power: 5 mW (5 mVA) Max. power: 7 W (7 VA)
High Current Rating:
If higher loads must be switched through one or more of the contacts, the minimum and maximum values of
the contact(s) changes to:
Min. voltage: 15V ac/dc Max. voltage: 250V ac/dc
Min. current: 30 mA ac/dc Max. current: 6 A (ES-FA-9AA) and 7A (ES-FA-11AA)
Min. power: 5 W (5 VA) Max. power: 200 W (1,500 VA)
Mechanical life: 50,000,000 operations
Electrical life: ES-FA-9AA: 150,000 operations (typical, @ 200 W (1,500 VA) switched power, resistive load) ES-FA-11AA: 130,000 operations (typical, @ 200 W (1,750 VA) switched power, resistive load)
Note: Transient suppression is recommended when switching inductive loads. Install suppressors across load. Never install suppressors across output contacts.
>
TI
m
-<
1 O
a c
r­m
PICO-GUARD CONTROLLERS
E-STOP/GUARD MONITORING
SAFETY MAT MONITORING
MUTING MODULES
Output Response Time
25 milliseconds typical
Input Requirements
Input switch must have one or two normally closed contacts capable of switching 40 to 100 mA @ 13 to 27V ac/dc. Reset switch must have one normally open contact capable of switching 20 to 30 mA @ 13 to 27V ac/dc.
EXTENSION MODULES
INTERFACE MODULES
Minimum OFF-State Recovery Time
250 milliseconds
Status Indicators
Power ON K1 energized K2 energized
Construction
Polycarbonate housing
Environmental Rating
Rated NEMA 1; IEC IP40, Terminals IP20
Mounting
Mounts to standard 35 mm DIN rail track. Safety Module must be installed inside an enclosure rated NEMA 3 (IEC IP54), or better.
Vibration Resistance
10 to 55Hz @ 0.35 mm displacement per IEC 68-2-6
Operating Conditions
Temperature: 0° to +50° C
Relative humidity: 90% @ +50° C (non-condensing)
Certifications
For a list of certifications see page 237.
Wiring Diagrams
1-Channel: WD048 (p. 275)
2-Channel: WD049 (p. 276)
More information online at bannerengineeringx^m 115
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
Contents table
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18
page 19 p.19
page 20 p.20
page 21 p.21
page 22 p.22
page 23 p.23
page 24 p.24
page 25 p.25
page 26 p.26
page 27 p.27
page 28 p.28
page 29 p.29
page 30 p.30
pdf-page pdf di En 2008-10-42-16