Switchgear overview
8,2 kOhm Monitoring resistor
Safety contact edgeEvaluation electronics
Safety switchgear are used in conjunction with safety contact elements wherever the secureprotection of individuals and equipment is required. The safety switchgear presented here
employ the quiescent current principle for monitoring the safety contact elements as this
meets the high demands for fault recognition and safety. The safety level provided is at-
tested to by approvals from the BG and TÜV for use up to safety category 3 in accordance
with EN 954-1.To monitor the quiescent current, a monitoring resistor is mounted at the end
of the signal transmitter line. If the setpoint quiescent current is flowing, the output relays are
activated and the switching contacts are closed. If the switching element is activated or the
safety circuit is interrupted, the relay switch contacts open. The relay switch states and the
applied operating voltage are indicated by LEDs.
Safety Considerations
The following risk chart reproduced from EN 954-1 offers instructions for selecting thesafety system category. The selection of the appropriate safety combination and its
safety level is the responsibility of the design or construction engineer. The instructions
shown do not release the design or construction engineer from the obligation to observe
all relevant standards in the design of the safety equipment.
KategorieB1234
S Degree of injury S1Light (generally reversible) injuriesS2Severe (generally irreversible) injuries F Frequency and/or duration of the hazard F1Seldom to frequentlyF2Frequent to continuous P Opportunity to avoid the hazard P1Possible under certain conditionsP2nearly impossible >
P2P1P2P1F2F1S2S1
Category selection B, 1 - 4 categories for controller components relevant to safetyPreferred category for reference points
Possible category requiring additional measuresExcessive measure in view of the hazard >