| | | ASCÛ | | |
| | | Bus Controls | | |
| | | |
| | | |
| | | Automation Operator Specifications All of the operators listed below are intended for use on clean, dry air or inert gas filtered to 50 micrometers or better. To prevent freezing, the dew point of the media should be at least 18T (-8°C) below the minimum temperature to which any portion of the clean air or gas system could be exposed. Instrument air, in compliance with ANSI/ISA Standard S7.3-1975 (R1981), exceeds the above requirements and is, therefore, an acceptable medium for these valves. | | |
| | | |
| | | Intrinsically Safe Piezo | | |
| | | | | | | | | | Operator Parts in Contact with Fluids | | | | Cover | Zenite (LCP) | | | | Adapter | Ryton (PPS) | | | | Guide | Ryton (PPS) | | | | Piston | Delrin (CA) | | | | Stem | PC/PBT | | | | Manual Operator Gasket | Santoprene | | | | O-Ring & U-Cup Seals | NBR, FKM | | | | | | | | | |
| | | Ordering: When ordering the IS Piezo Valve, use the appropriate prefix from the table below. | | |
| | | |
| | | Valve Catalog Number Prefix | | |
| | | |
| | | | | | | | | | | | Connector Types | Current Type | | | | Ultra Low | Intermediate | Low | | | | 1.4mA - 2.3mA | 1.7mA - 3.7mA | 5.1mA - 9.3mA | | | | M12 4 Pole | PIA | PIB | PIC | | | | DIN | PID | PIE | PIF | | | | | | | | | | | |
| | | |
| | | |
| | | Zenite and Delrin are trademarks of Dupont. Ryton is a trademark of Philipps 66. Santoprene is a trademark of Advanced Elastomer Systems. | | |
| | | Each version will operate anywhere within the range of 6-27 volts. The graph shows the electrical characteristics of the three catalog varieties. The response time for all three versions will increase slightly as the voltage decreases towards the lower limit of 6 VDC. | | |
| | | |
| | | | | | | | | | Entity | Groups A-D | | | | Parameters | V max - 30 VDC | | | | I max - 100 mA | | | | Capacitance = 0 | | | | Inductance = .264 mh | | | | | | | | | |
| | | |
| | | Enclosure Type: NEMA 4, 4X Input Voltage: 6-30VDC Current Usage: 1.4 - 9.3 mA Power Consumption: 0.0084 - 0.24 watts Response Time: < 350 ms Ambient Temperature: 32°F to 140T | | |
| | | Low Current | | |
| | | |
| | | |
| | | Momentary Manual Operator standard. Approvals: FM - approved under J.I. 3W8A8AX CSA pending - file under LR - 13976-116C ATEX EEx ia IIC T6 @ 60° pending. | | |
| | | Intermediate Current Ultra Low Current | | |
| | | □ ü | | |
| | | |
| | | |
| | | 6 8 10 12 14 16 18 20 22 24 26 28 Input Voltage (VDC) | | |
| | | |
| | | |
| | | 5.60 R2 | | |
| | | |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |