ASCÛ
Bus Controls
Automation Operator Specifications
All of the operators listed below are intended for use on clean, dry air or inert gas filtered to 50 micrometers or better. To prevent freezing, the dew point of the media should be at least 18T (-8°C) below the minimum temperature to which any portion of the clean air or gas system could be exposed. Instrument air, in compliance with ANSI/ISA Standard S7.3-1975 (R1981), exceeds the above requirements and is, therefore, an acceptable medium for these valves.
Intrinsically Safe Piezo
Operator Parts in Contact with Fluids
Cover
Zenite (LCP)
Adapter
Ryton (PPS)
Guide
Ryton (PPS)
Piston
Delrin (CA)
Stem
PC/PBT
Manual Operator Gasket
Santoprene
O-Ring & U-Cup Seals
NBR, FKM
Ordering:
When ordering the IS Piezo Valve, use the appropriate prefix from the table below.
Valve Catalog Number Prefix
Connector Types
Current Type
Ultra Low
Intermediate
Low
1.4mA - 2.3mA
1.7mA - 3.7mA
5.1mA - 9.3mA
M12 4 Pole
PIA
PIB
PIC
DIN
PID
PIE
PIF
Zenite and Delrin are trademarks of Dupont.
Ryton is a trademark of Philipps 66.
Santoprene is a trademark of Advanced Elastomer Systems.
Each version will operate anywhere within the range of 6-27 volts. The graph shows the electrical characteristics of the three catalog varieties. The response time for all three versions will increase slightly as the voltage decreases towards the lower limit of 6 VDC.
Entity
Groups A-D
Parameters
V max - 30 VDC
I max - 100 mA
Capacitance = 0
Inductance = .264 mh
Enclosure Type: NEMA 4, 4X Input Voltage: 6-30VDC Current Usage: 1.4 - 9.3 mA Power Consumption: 0.0084 - 0.24 watts Response Time: < 350 ms Ambient Temperature: 32°F to 140T
Low Current
Momentary Manual Operator standard.
Approvals:
FM - approved under J.I. 3W8A8AX
CSA pending - file under LR - 13976-116C
ATEX EEx ia IIC T6 @ 60° pending.
Intermediate Current Ultra Low Current
ü
6 8 10 12 14 16 18 20 22 24 26 28 Input Voltage (VDC)
5.60 R2