Datasheet Type
AS9 (two wire)
Technical data
Auxiliary voltage: 230V ±10%, 50 Hz
Power consumption: Approx. 2.3 VA...5 VA
Sensor circuitry (intrinsically safe „ ,, .
, ./ . , ' See VE9 resp. LW9 below
and self monitoring):
Relay-switching current circuit: Limit value relay with zero potential switch-over contacts.
Relay breaking capacity: Switching function: Response delay::
Max. 1 A, max. 250 VAC, max. 250 VA When the limit value is reached, the relay is released. 1 sec. ±50%
Output Type AS9.1: Output Type AS9.2: Output Type AS9.3:
Switching state:
Type of protection:
Temperature range:
Dimensions:
One zero potential switch-over contact. Two zero potential switch-over contacts. Three zero potential switch-over contacts.
When the limit value is reached, the red LED lights up.
IP54
-20°C to 40°C
H x W x D: 132 x 71 x 137 mm
Ex-classification: with Type VE9 / [EEx ia] IIC
LW9:
For application in Ex-environment
with VE9 for the use with sensor AF1S, AF21, AF23, AF33, AF35, AF42. types:
Sensor types for all other
AF6, AF24, AF26, AF31, AF32, AF36.
applications:
Conductive probes with LW9 for
LS11, LS12, LS13, LS21.
the operation with probe types:
Type VE9 / LW9: Local electronic
Aquasant AG Ph: +41 (0)56 437 4080
Schartenstrasse 111 page 1 of 4 Fax: +41 (0)56 437 4089
CH-5430 Wettingen with reservation of technical modifications Information@aquasant.com