95006025/6/04E
Datasheet Type
AS9-E24 (two wire)
Technical data Auxiliary voltage Ub:
24 V AC/DC ±10%, protected against polarity reversal, low safety voltage (SELV)
Power consumption: Approx. 3 VA
Sensor circuitry (intrinsically safe
See VE9 resp. LW9 below
and self monitoring):
Relay-switching current circuit: One limit value relay with zero potential switch-over contacts.
Relay breaking capacity: Switching function: Response delay:: Output:
Switching state: Type of protection: Temperature range: Dimensions:
Max. 0.5 A, max. 48 VAC, max. 50 VA
When the limit value is reached, the relay is released.
1 sec. ±50%
Two zero potential switch-over contacts.
When the limit value is reached, the red LED lights up.
IP20
-20°C to 40°C
European standard board 100 x 160mm
Ex-classification: with Type VE9: [EEx ia] IIC For application in Ex-environment
with VE9 for the use with sensor AF1S, AF21, AF23, AF33, AF35, AF42. types:
Sensor types for all other
AF6, AF24, AF26, AF31, AF32, AF36.
applications:
Conductive probes with LW9 for
LS11, LS12, LS13, LS21.
the operation with probe types:
Type VE9 / LW9: Local electronic
Aquasant AG Schartenstrasse 111 CH-5430 Wettingen Switzerland
page 1 of 4 with reservation of technical modifications
www.aquasant.com
Ph: +41 (0)56 437 4080 Fax: +41 (0)56 437 4089 Information@aquasant.com 6/04
|
|