Recordings • 4MBytes removable flash card memory for data storage • • WCAP option - advanced waveform capture function oncurrents and L-N voltages. The instrument can store up to
10 + 200 waveforms before and after a threshold overcome,
with a resolution from 8 to 32 samples (depending on the
number of waveforms). The WCAP option includes a
second selectable function: Min/Avg/Max values calculation
and recording (see previous paragraph) Up to 10 programmable recordings with different start andstop time. Different type of recordings can be chosen:-import/export active, reactive and apparent powerdemand with programmable average time. The average
period can be syncronized by a digital input-instantaneous read values selected between the mainparameters. The recording interval time is
programmable between 1 and 9999 seconds-instantaneous min/max values measured during therecording interval time. The recording interval time is
programmable between 1 and 9999 minutes-voltage and current harmonic values measured duringthe recording interval time. The recording interval time
is programmable from 1 to 60 minutes • The CPU2 option includes 1MBytes non-volatile datamemory. Depending on the CPU2 configuration the
following information (already described in the “Power
Quality” paragraph) can be recorded:-sags and swells events (VDROP option). The occurringdips and overvoltage over a programmable threshold
are detected and the instrument records the date and
time of the event, the lenght and the RMS value of 100
+100 half-cycles before and after the event-min / avg / max values of the main measured parameterswith continuous sampling and 1 cycle minimum • Event, alarm and digital outputs ON/OFF recording. Theinstrument records the status change of 8 programmable
set points, the digital outputs ON/OFF and the instrument
supply ON/OFF. All the events are integrated by date and
time reference • Time-of-Use (TOU) programmable data recording. TheTOU function stores the energy consumption in different
registers according the programmed time-scheme. A group
of 120 registers give the situation of the previous and
current day, and of the previous and current month. This
feature is designed to fit different tariff structures. It’s
possible to program up to 10 daily tariff schedules
containing up to 3 tariffs and 8 tariff changes. Eachschedule can be assigned to the days of the week andmonths as requested. Up to 20 holidays can be assigned
to the lowest tariff. A diagnostic algorithm checks and
notifies any setup overlapping. >
2 >
Main Features
Measurements • Three-phase 3-wire or 4-wire unbalanced load operation,single-phase and direct current. • Direct measurement up to 600 (750)V >
AC • The instrument can accept different signals from any typeof measuring transducer, including flexible Rogowski
transducers. The required current channel type is easily
selectable by the instrument menu. This flexibility allows to
connect the following current tranducers:-voltage output
manufacturers of clamps (1, 2, 3V >
AC-DC full scale)-current output clamps (1, 5A >
AC full scale)-Rogowski flexible clamps (40 or 100mV/kA)-direct insertion up to 600V >
AC (1, 5, 20A >
AC full scale)-current tranducer signals (1, 2, 3, 10V >
AC-DC full scale) • A fourth current input is also provided specifically for themeasurement of earth leakage current • True RMS metering provides accurate measurement evenby distorted waveform • • Fully bi-directional, four-quadrant readings. 10 energycounters are available, the apparent power/energy is
splitted in four counters: import lagging, import leading,
export lagging, export leading Volts, Amps, Power, PF, Frequency, Energy, Min/Maxvalues, Demand, Harmonics, etc. The full version
instrument provides more than 600 measured/calculatedparameters and shows on the LCD more than 30 graphicalpages Power Quality • Individual & total harmonic distortion for voltage and currentup to the 50 • VMAX option - two functions are selectable: VDROP(previous paragraph) and Min/Avg/Max values calculation
and recording with one cycle resolution (20ms @ 50Hz).
This function allows to record up to 10 parameters selected
among voltage, current, power, PF and frequency. The datais viewed on the PC according EN50160 standard. • VDROP option - sags & swells detection on L-N voltageswith half cycle resolution (10ms @ 50Hz). Pre- and post-
trigger logging (100 +100 half cycles RMS values). The
detected events are recorded and a relay output can be
activated when a voltage anomaly occurs. The data is
viewed on the PC according EN50160 standard. >
th order. The harmonic content is representedlike even, odd and total • CPU2 option - the co-processor board perfoms thesimultaneous high-resolution sampling of voltage and
current, allowing the cycle-by-cycle power analysis for
50/60 Hz lines. The CPU2 board supports different
application like: VDROP, VMAX, WCAP... (see below). The
instrument with CPU2 board performs at the same time
the
wattmeter functions, the harmonic analysis, the basic
recording function and the selected cycle-by-cycle power
analysis function. >