10
Model
Airflow
Heating
Capacity
80/60ΊC
Water
Drop
Pressure
80/60ΊC
Water
Connections
80/60ΊC
Heating
Capacity
60/40ΊC
Water
Drop
Pressure
60/40ΊC
Water
Connections
60/40ΊC
Electrical
Heating
Capacity
3x400V-50Hz
Fans
Power
230V-50Hz
Fans
Current
230V-50Hz
Noise
Level
(3 m)
Weight
m3/h kW Pa kW Pa kW kW A dB(A) kg
RS 1000 P 1250 8,53 7200 2x3/4 6,50 2250 2x3/4 - 0,372 1,68 53 56
RS 1000 E 1300 - - - - - - 3/6/9 0,372 1,68 53 58
RS 1000 A 1300 - - - - - - - 0,372 1,68 53 51
RS 1500 P 1875 12,92 3200 2x3/4 10,62 8300 2x3/4 - 0,558 2,52 54 83
RS 1500 E 1950 - - - - - - 4/8/12 0,558 2,52 54 87
RS 1500 A 1950 - - - - - - - 0,558 2,52 54 75
RS 2000 P 2500 18,11 8300 2x3/4 14,10 4400 2x3/4 - 0,744 3,36 55 107
RS 2000 E 2600 - - - - - - 6/12/18 0,744 3,36 55 114
RS 2000 A 2600 - - - - - - - 0,744 3,36 55 96
RS 2500 P 3125 22,20 3000 2x3/4 18,10 8650 2x3/4 - 0,930 4,20 56 121
RS 2500 E 3250 - - - - - - 6/12/18 0,930 4,20 56 128
RS 2500 A 3250 - - - - - - - 0,930 4,20 56 108
RS 3000 P 3750 28,39 4440 2x3/4 21,47 3910 2x3/4 - 1,116 5,04 57 135
RS 3000 E 3900 - - - - - - 8/16/24 1,116 5,04 57 142
RS 3000 A 3900 - - - - - - - 1,116 5,04 57 122
RM 1000 P 1800 10,27 850 2x3/4 8,72 4250 2x3/4 - 0,510 2,22 54 56
RM 1000 E 1850 - - - - - - 3/6/9 0,510 2,22 54 58
RM 1000 A 1850 - - - - - - - 0,510 2,22 54 51
RM 1500 P 2700 16,98 3250 2x3/4 13,86 6700 2x3/4 - 0,765 3,33 55 83
RM 1500 E 2775 - - - - - - 4/8/12 0,765 3,33 55 87
RM 1500 A 2775 - - - - - - - 0,765 3,33 55 75
RM 2000 P 3600 23,60 8000 2x3/4 18,58 4900 2x3/4 - 1,020 4,44 56 107
RM 2000 E 3700 - - - - - - 6/12/18 1,020 4,44 56 114
RM 2000 A 3700 - - - - - - - 1,020 4,44 56 96
RM 2500 P 4500 29,16 3860 2x3/4 23,18 4050 2x3/4 - 1,275 5,55 57 121
RM 2500 E 4625 - - - - - - 6/12/18 1,275 5,55 57 128
RM 2500 A 4625 - - - - - - - 1,275 5,55 57 108
RM 3000 P 5400 35,78 6790 2x3/4 28,65 7150 2x3/4 - 1,53 6,66 58 135
RM 3000 E 5550 - - - - - - 8/16/24 1,53 6,66 58 142
RM 3000 A 5550 - - - - - - - 1,53 6,66 58 122
RG 1000 P 2700 13,10 1300 2x3/4 11,31 6850 2x3/4 - 0,765 3,33 55 61
RG 1000 E 2775 - - - - - - 5/10/15 0,765 3,33 55 63
RG 1000 A 2775 - - - - - - - 0,765 3,33 55 55
RG 1500 P 3600 20,30 4500 2x3/4 16,72 9400 2x3/4 - 1,020 4,44 56 89
RG 1500 E 3700 - - - - - - 7,5/15/22,5 1,020 4,44 56 93
RG 1500 A 3700 - - - - - - - 1,020 4,44 56 80
RECESSED WINDBOX S,M,G |
Self-supporting casing constrution made of galvanized plated steel, ready to be
installed recessed in a false ceiling.
The inlet grille and blow-out nozzle are integrated in a single white frame, colour
RAL 9016. Other colours are available on request.
Low noise centrifugal double inlet fans driven by an external rotor motor with built
in thermal protection contact. Provided by five speed selection.
P type includes water heated coils. E type includes electrical shielded elements,
three power stages with power switches included. A type is without heating,
air only.
Anodised aluminium blow-out vanes, airfoil shaped, pitch angle adjustable
each side.
Control panel and 20m of telephonic cable with fast connectors type RJ45
(Plug & Play), included. Optional: Interface to connect to BMS.
Characteristics
Commercial And Industrial
Recessed Air Curtains
Specifications
|
|