AirCare VariPhase ™
Overview
This AC0yB14 is a “Network Only” version of the
AirCare V-Series VariPhase™ line. Targeted at Fan
Filter Unit (FFU) applications the unit offers 3-wire
Phase-control speed conditioning along with a
contact switch feedback for go/no-go fan monitoring
and feedback. The AC0yB14 uses MODBUS®RTU
network communication and is compatible with all
the AirCare Console and System controllers.
The AC0yB14 enables single-phase AC PSC
motors to run at optimized speeds and reduce
motor heating, energy consumption and audible
noise.
Features
• Variable Voltage Phase-Control
• 115V, 230V and 277V models
• Up to 3 Amp load capability
• 3-wire option reduces motor hum and
increases efficiency at lower speeds
• RS485 network connectivity (MODBUS
RTU protocol) using either:
o Twisted-pair cable.
o RJ45 Connector
• Monitoring input for pressure switch or
similar open/closed contact switch.
• Minimum Speed Set Point (register set)
• Soft-start reduces motor start current
• LED indicates board status
Specification Summary
• Automatic Selection of 50/60Hz
• Simple connections
o ¼” Spade terminals for power
o ¼” Spade terminals for sensor fdbk.
o 7 way terminal block or RJ-45 contacts for
communications (optional)
• LED diagnostics
o Green – Board OK, valid comms link
o Red – Fault, no comms link
• Fuse Ratings
o 5A 250V or 3A 300V
• MODBUS RTU Protocol
o RS485 9600,8,n,1
• Minimum speed set by MODBUS register
• Open-frame PCB
o Mount with standard nylon standoffs
• 0-50°C operating temperature
• Low-profile design
o 3.95” x 3.95” x 1.0”
Model Matrix
Product Description
AC0yB14 is an application specific Network
only version of the AirCare VariPhase™ VSeries
controller. Providing Open-loop control
and NC/NO sensor switch contact, this unit is
targeted at baseline Fan Filter Installations.
AC0yB14 is very simple to install and configure.
The only necessary electrical connections are an
AC supply, a motor load and RS485 wiring.
The Units MODBUS address is set from 1 to 240
using an on-board DIP switch.
The motor load may be connected in standard
two-wire mode, or with the auxiliary winding
permanently powered in 3-wire mode (see wiring
diagram). A dedicated spade-terminal is (AUX)
provided.
AC0yB14 feedback input (IN) can be wired
directly to an external contact, such as a pressure
switch or a motor thermal cut-off switch.
Connecting an external NO/NC contact can be
done through either the 7 way terminal block or
¼” Spade terminals mounted above the 7-way.
This NO/NC input is comparable to the ANA1
input on standard VariPhase(s) units and can be
used for monitoring go/no-go performance of a
fan system (i.e. differential pressure switch
monitoring).
Model Voltage
Rating(AC)
Current
Rating
AC01B14 115V 3.0A
AC02B14 230V 3.0A
AC03B14 277V 3.0A
AC01B14
AC02B14
AC03B14
Email: info@aircareautomation.com Website: www.aircareautomation.com
8204 (. Lamar, Suite B-11 Austin, TX 78753 Tel: (512) 249-7526 Fax: (512) 275-6155
Rev1.4 11/08
-SERIES
CE approved and ETL certified to UL508C.. Contact factory for more details.
|
|